Laserfiche WebLink
Gateway Park Center PERKINS+WILL <br /> 810495.000 <br /> 12/06/18 <br /> <br /> <br />STRUCTURAL-SEALANT-GLAZED CURTAIN WALLS <br /> 08 44 23 - 10 <br /> <br /> <br />3. Water Penetration: Areas shall be tested according to ASTM E 1105 at a <br />minimum uniform and cyclic static-air-pressure differential of 0.67 times the <br />static-air-pressure differential specified for laboratory testing in "Performance <br />Requirements" Article, but not less than 6.24 lbf/sq. ft., and shall not <br />evidence water penetration. <br />a. Test Area: One bay wide, but not less than 30 feet, by one story of <br />structural-sealant-glazed curtain wall. <br />b. Perform a minimum of three tests in areas as directed by Architect. <br />4. Water Spray Test: Before installation of interior finishes has begun, areas <br />designated by Architect shall be tested according to AAMA 501.2 and shall not <br />evidence water penetration. <br />a. Test Area: A minimum area of 75 feet by one story of structural- <br />sealant-glazed curtain wall. <br />D. Structural-sealant-glazed curtain walls will be considered defective if they do not <br />pass tests and inspections. <br />E. Prepare test and inspection reports. <br />END OF SECTION