<br />CTA Project No. 19-0035-001-01 16120-4 Golden Shores Street Lighting <br />October 12, 2020 SIB Bid No. 20-09-01 <br />box, junction box, or manhole. Provide permanent, waterproof, non-metallic heat <br />shrinkable tube cable markers in 3/16-inch letters. <br />D. Signs <br /> Warning signs shall comply with OSHA requirements and reasonable safety precautions. <br />E. Underground Identification <br /> During backfilling of each exterior underground electrical, signal or communication cable, <br />conduit, or ductbank, install a continuous underground-type plastic with foil backed line, <br />marker, located directly over the buried line at six (6) inches to eight (8) inches below <br />finished grade. <br /> <br />- END OF SECTION - <br />