Laserfiche WebLink
G$NMAI, SAUC`I'UItAI, NOTES <br />1_ GENERAL= <br />THE STRUCTURAL SYSTEM FOR THE BUILDING HAS BEEN DESIGNED IN ACCORDANCE WITH THE <br />FLORIDA BUILDING CODE, 2020 EDITION. <br />THE STRUCTURE WAS DESIGNED TO BE SELF-SUPPORTING AND STABLE FOLLOWING INSTALLATION OF <br />ALL COMPONENTS AS INDICATED IN THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE <br />CONTRACTOR TO DETERMINE THE SEQUENCE OF ERECTION PROCEDURES (INCLUDING <br />IMPLEMENTATION OF TEMPORARY SHORING, BRACING, ETC_) AND TO ENSURE SAFETY THROUGHOUT THE <br />PERIOD OF CONSTRUCTION. <br />THE CONTRACTOR SHALL USE THE STRUCTURAL DRAWINGS IN CONJUNCTION WITH THE ARCHITECTURAL, <br />MECHANICAL AND ELECTRICAL DRAWINGS TO COORDINATE LOCATION OF DEPRESSED SLABS, <br />SLOPES, DRAINS, OUTLETS, RECESSES, OPENINGS, REGLET5, BOLT SETTINGS, SLEEVES, DIMENSIONS, <br />ETC. POTENTIAL CONFLICTS SHALL BE TRANSMITTED TO THE ARCHITECT AND ENGINEER BEFORE <br />PROCEEDING WITH THE WORK. CONTRACTOR TO PROVIDE ADEQUATE TIME FOR RESPONSE FROM <br />ARCHITECT/ENGINEER, NO PENETRATION SHALL BE MADE IN ANY STRUCTURAL MEMBER WITHOUT A <br />PREVIOUS WRITTEN APPROVAL OF THE ENGINEER OF RECORD. IF ANY ERRORS, OMISSIONS OR <br />POTENTIAL CONFLICTS APPEAR IN THE DRAWINGS, SPECIFICATIONS, OR OTHER DOCUMENTS, THE <br />CONTRACTOR MUST NOTIFY THE ARCHITECT AND ENGINEER, IN WRITING, OF THE SAME PRIOR TO <br />PROCEEDING WITH THE WORK IN QUESTION. IN THE EVENT THAT THE CONTRACTOR FAILS TO GIVE <br />NOTICE, OR PROVIDE SUFFICIENT TIME FOR A RESPONSE, CONTRACTOR 15 RESPONSIBLE FOR THE <br />RESULTS OF SUCH ERRORS OR OMISSIONS, AND FOR ALL COSTS FOR RECTIFYING SAME AND FOR ANY <br />DELAYS OR ANY OTHER COSTS INCURRED BY SAME, <br />2_ CONCRETE: <br />ALL CONCRETE TO ATTAIN A MINIMUM ULTIMATE COMPRE551VE STRENGTH OF 5,000 R51 IN 28 DAYS, <br />AGGREGATES TO BE CLEAN AND WELL GRADED, MAXIMUM 51ZE I' CONCRETE SLUMP= 3' MIN. TO 5' MAX. VERTICAL CONCRETE. <br />DROP NOT TO EXCEED 8'. <br />3_ CONCRETE COVER -- <br />TO BE AS FOLLOWS: BOTTOM TOP SIDES <br />FOOTINGS 3' 2' 3" <br />COLUMNS - - 15" <br />BEAMS 1.5' 1.5" 1.5" <br />SLABS 1' 1' 1" <br />4_ REINFORCING STEEL -- <br />TO BE NE HIGH STRENGTH BILLET STEEL DEFORMED AS PER ASTM A-305, AND CONFORMING TO ASTM <br />A-615, GRADE 60. LAP CONTINUOUS BARS 30-5AR DIAMETERS, UNLESS OTHERWISE NOTED IN PLANS. <br />HOOK DISCONTINUOUS ENDS OF ALL TOP BARS. REINFORCING STEEL TO BE DETAILED AND <br />FABRICATED IN ACCORDANCE WITH "MANUAL OF STANDARD PRACTICE OF DETAILING REINFORCING <br />CONCRETE STRUCTURES", AND THE ACI BUILDING CODE 318, LATEST EDITION. SUBMIT SHOP DRAWINGS <br />FOR APPROVAL BY ENGINEER BEFORE FABRICATION. <br />5_ APPLICABLE CODE= <br />- THE FLORIDA BUILDING CODE 2020 lith EDITION) AND ALL ITS REFERENCE[) STANDAIRDS <br />- ASCE 1-16 <br />ALL STRUCTURAL ELEMENTS, EXPOSED TO WIND, HAVE BEEN DESIGNED <br />PER THE GUIDELINES OF THE ASCE 1-16 CODE_ <br />WIND 5PEED =115 MPH. <br />EXPOSURE = D <br />RISK CATEGORY = l II ) <br />Kd = 0.85 <br />INTERNAL PRESSURE COEFFICIENT +/- 0.18 <br />6_ SPECIALTY ENGINEERED SYSTEMS: <br />ITEMS DESIGNATED ON DRAWINGS THAT REQUIRE DESIGN BY A SPECIALTY ENGINEER SHALL BE <br />DESIGNED, DETAILED, FABRICATED AND ERECTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE <br />FLORIDA BUILDING CODE BASED ON LAYOUT AND CONFIGURATION AS SHOWN ON ARCHITECTURAL <br />DRAWINGS. THE SPECIALTY ENGINEERED SYSTEM SHALL BE DESIGNED TO RE515T THE GRAVITY <br />LOADS AND COMPONENT AND CLADDING WIND PRESSURES INDICATED ON THIS DRAWING. SHOP <br />DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED THAT ARE DATED, SIGNED AND SEALED BY A <br />PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF FLORIDA. <br />SPECIALTY ENGINEERED ITEMS ON THIS PROJECT INCLUDE= <br />a) WOOD TRUSSES. <br />b) LOUVERS. <br />c) PRECAST CONCRETE VENT <br />I_ MASONRY= <br />A. ALL CONCRETE BLOCK TO BE GRADE N-2, CONFORMING TO ASTM C-90, WITH A MINIMUM NET <br />AREA COMPRESSIVE STRENGTH OF 1,900 PSI, AND A PRISM STRENGTH OF 1,500 PSI (MINIMUM). <br />MORTAR SHALL BE TYPE M, WITH A MINIMUM STRENGTH OF 2,500 P51 (USE PORTLAND TYPE <br />CEMENT). TEST MASONRY UNITS AND MORTAR BY TESTING LAB AT A RATE OF EVERY 1,000 <br />SQUARE FEET OF WALLS ERECTED. <br />B_ MASONRY WALLS SHALL BE REINFORCED HORIZONTALLY WITH 8 GAUGE DEFORMED GALVANIZED <br />STEEL, SPACED AT 16" C/C VERT. EXTEND HORIZONTAL REINFORCING 4' INTO ADJACENT <br />COLUMNS. PROVIDE TRUSS TYPE FOR NON -REINFORCED MASONRY AND LADDER <br />TYPE FOR REINFORCED MASONRY. <br />C. FOR VERTICAL REINFORCEMENT, SEE SCHEDULE AND LAP 46 BAR DIAMETERS MINIMUM. PROVIDE <br />FULL BED OF MORTAR FOR REINFORCED MASONRY. <br />D. AT ALL INTERIOR NON-BEARING BLOCK WALLS, MUST PROVIDE A TIE- BEAM 8"x12" WITH FOUR #5 <br />CONT. AND #3 TIES AT 48' C/C, <br />E. PROVIDE CLEANOUTS WHEN GROUTING BLOCK CELLS, AND CLEAN OUT BLOCK CELLS OF ALL <br />MORTAR DROPPINGS. MAXIMUM VERTICAL DROP FOR GROUTING 15 4'-0" <br />F. AT THE END OF EACH DAY COVER ALL MASONRY WALLS. <br />S STRUCTURAL STEEL -- <br />SHALL CONFORM TO ASTM A441 OR A512 GRADE WITH A MINIMUM YIELD STRESS OF 50 KSI, DETAILED, <br />FABRICATED AND ERECTED IN ACCORDANCE WITH "AI5C' SPECIFICATIONS, LATEST EDITION. <br />STRUCTURAL TUBE SECTIONS SHALL CONFORM TO ASTM A500 GRADE B (fy = 4(o KSI). ALL TUBES TO <br />BE CONCRETE FILLED. BOLTS SHALL CONFORM TO ASTM A325 OR ASTM A490, UNLESS OTHERWISE <br />NOTED IN PLANS. SUBMIT SHOP DRAWINGS FOR APPROVAL BEFORE FABRICATION. <br />9_ WELDING -- <br />ALL WELDING TO BE DONE BY DADE COUNTY CERTIFIED WELDERS HOLDING CURRENT WELDING <br />CERTIFICATES, AND MUST PRESENT SAME AT JOB 51TE AT ALL TIMES. <br />ALL WELDING PER PLANS AND PER GUIDELINES OF THE AMERICAN WELDING SOCIETY <br />10_ SHOP DRAUIINGS= <br />NO SHOP DRAWING SHALL BE SUBMITTED FOR ARCHITECT/ENGINEER'S REVIEW UNTIL AFTER THEY <br />HAVE BEEN REVIEWED AND NOTED FOR CONSTRUCTION METHOD, DIMENSIONING, AND OTHER TRADE <br />REQUIREMENTS BY THE CONTRACTOR, AND STAMPED WITH THE CONTRACTOR'S APPROVAL SEAL. <br />ENGINEER ASSUMES NO RESPONSIBILITY FOR DIMENSIONS, QUANTITIES, ERRORS OR OMISSIONS, AS A <br />RESULT OF CHECKING AND REVIEWING ANY SHOP DRAWINGS. ANY ERRORS OR OMISSIONS MUST BE <br />MADE GOOD BY CONTRACTOR, IRRESPECTIVE OF RECEIPT, CHECKING OR REVIEW OF DRAWINGS BY <br />ENGINEER, AND EVEN THOUGH WORK IS DONE IN ACCORDANCE WITH SUCH SHOP DRAWINGS. <br />11_ EPDXY 5ASED ANCHORS_ <br />FOR ANCHORING REINFORCING STEEL OR RODS IN EXISTING CONCRETE USE: <br />- NSE 2411 BY "HILTI" <br />- POWER FAST BY "POWERS/RAWL" <br />- ALLIED GOLD A-1000 BY "ALLIED FASTENER AND TOOL" <br />- OR ANY OTHER AVAILABLE PRODUCT PROVEN EQUAL. <br />DRILL HOLES 1/8" MIN, BIGGER THAN THE DIAMETER OF THE BAR OR THREADED ROD, <br />THE DEPTH OF THE HOLES TO BE AS INDICATED IN PLANS BUT NEVER LESS THAN <br />MINIMUM INDICATED BY MANUFACTURER ALL HOLES MUST BE THOROUGHLY CLEANED <br />FROM DUST AND DRY BEFORE POURING THE EPDXY GEL. IN THE EVENT OF LOST OR <br />MISPLACED DOWELS INSTALLATION, THE STRUCTURAL ENGINEER (OR REPRESENTATIVE) <br />MUST INSPECT HOLES PRIOR TO BEGINNING OF EPDXY INJECTION AND BARS <br />INSTALLATION. <br />12_ DETAILS AND SECTIONS -- <br />ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL, AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />UNLESS A DIFFERENT DETAIL, OR SECTION, IS SHOWN, <br />13_ DESIGN LOADS_ <br />WOOD TRUSSES <br />DEAD LOAD = 25 PSF <br />LIVE LOAD = 20 PSF <br />P1kEFAt WOOD IrkusSES & GI1kDE1kS CONNECIroks SCHEDULE <br />O +I'IO <br />OnS $�p Y <br />LESS O I WIS <br />NOIiD <br />�ONN9&Ok 4LOVOL9 LOAD► VALUES albs) <br />NAIL 5 �t <br />QU <br />LIPADA <br />AL <br />�" <br />A LOAD <br />Pa4ll IL TO '4 L <br />LA I AL, L AD <br />lute] NDI�ULAk TO 'gyp <br />O <br />META 20 W/TSS <br />1450 <br />340 <br />195 <br />(8)-10c1 x 11/2" NAILS <br />FL 114-13 <br />BO <br />DETAL 20 <br />2400 <br />2000 <br />1505 <br />(15)-10c1 x 11/2" NAILS <br />FL 11413 <br />C�] 3 <br />6 12" <br />RT5-1 <br />+ 10'-4" <br />0 x 12 <br />2-#S <br />WIND LOAD PRESSURES <br />FOR ROOFING DESIGN (ASD) <br />ZONE <br />PRESSURE <br />I <br />-l2 PSF <br />2e <br />-113 PSF <br />C3) <br />-131 PF <br />2r <br />-107 PSF <br />NET WIND LOAD PRESSURES <br />FOR TRUSS DESIGN (ASD) <br />(GROSS PRESSURES HAVE BEEN REDUCED BY 5 PSF TO OBTAIN NET PRESSURES) <br />ZONE <br />PRESSURE <br />JACK TRUSSES <br />ALL OTHER TRUSSES <br />1 <br />-61 PSF <br />- 44 1=5F <br />02e <br />-108 PSF <br />-92 PSF <br />C3) <br />-132 PSF <br />-01 PSF <br />2r <br />-102 PSF <br />-66 PSF <br />WIND LOAD PRESSURE FOR WINDOWS, <br />DOORS AND LOUVERS. (ALLOWABLE) <br />(POUNDS PER SQUARE FOOT) <br />+TOP OF <br />$.$I <br />gLEV, <br />ZONE 0 <br />ZONE5 <br />AREA <br />��. <br />�' <br />POSITIVE <br />INEGATIVE <br />POSITIVE <br />NEGATIVE <br />No. <br />10 ft2 to 25 ft2 <br />+413 <br />- 53 <br />+413 <br />- 65 <br />NOTES: <br />L- ZONE ( 15 DEFINED AS ANY DOOR OR WINDOW WITHIN a =3'-O' <br />FROM A Y CORNER OF THE BUILDING, ALL OTHER LOCATIONS <br />ARE DEFINED AS ZONE 4 <br />2,-VALUE5 INDICATED CAN BE INTERPOLATED. <br />NOTE. THE WIND PRESSURES INDICATED ON THE TABLES ARE TO BE USED <br />WITH LOAD COMBINATIONS OF A5CE-1-10 <br />L1/4 L1/4 OR I L2/4 L2/4 OR CANT. <br />WHICHEVER IS GREATER WHICHEVER IS GREATER <br />"C" B R —1 TOP BAR I STOP BA <br />BOTTOM BAR LAP 24 BAR DIA. <br />INTERMEDIATE <br />REINFORCING STIRRUPS AS SCHEDULED <br />STD. HOOKS I I/2" COVER ALL SIDES <br />1 THRUOUT LI I L2 <br />tE <br />TYPICALAM DIAGRAM � <br />BOTTOM RAR <br />NOTES -- <br />L- - "C" BARS ARE TOP BARS AT NON -CONTINUOUS ENDS. <br />2 - "E" BARS ARE TOP BARS OVER RIGHT INTERIOR SUPPORTS. <br />3.- TOP BARS CALLED FOR AS CONTINUOUS, WHEN SPLICED, <br />SHALL BE SPLICED IN THE 1" 11DDLE THIRD OF THE SPAN. <br />4.- REFER TO INTERMEDIATE BEAM REINFORCING FOR ADDITIONAL REINFORCING. <br />5.- PROVIDE AT ALL NON-BEARING BLOCK WALLS, A TIE -BEAM Vx12" (MIN-AJJITH <br />2-S TOP ANP BOTTOM CONT., #3 TIES, 4 AT 12 "c/c EACH END, RAL. AT 45"c/c <br />TIE -BEAMS MUST BE DOWELED INTO WALLS AT EACH END, AT INTERSECTIONS, AT <br />INTERMEDIATE POINTS. <br />(o.- PROVIDE 2-#5 x5' -O" CORNER BARS (EXTEND 30" IN EACH DIRECTION FROM <br />CORNER) AT ALL NON-BEARING BLOCK WALLS. <br />EE <br />lYl rl <br />tEA M SH <br />0 <br />2r <br />2� Ol <br />EI�IIi EE- EACH END. <br />a EG- EAGN CORNER <br />MAAK <br />+TOP OF <br />$.$I <br />gLEV, <br />SIDE <br />(IN.) <br />W x H <br />AMWOkIdING <br />StkkupS <br />��. <br />�' <br />+I' <br />�' <br />2e <br />EF� <br />No. <br />SPA IN�G <br />T5-1 <br />+ V-0" <br />0 x 12 <br />2-'S <br />2 -*5 <br />I <br />C�] 3 <br />6 12" <br />RT5-1 <br />+ 10'-4" <br />0 x 12 <br />2-#S <br />2 -*5 <br />U 3 <br />Q 12" <br />R5-1 <br />+10'-4" <br />8 x 12 <br />2-#6 <br />2-#(o <br />Ll 3 <br />e 5" <br />NOTE: VALUES INDICATED ARE NET UPLIFT. <br />/-,4\UPLIFT DIAGRAM <br />SCALE: N.T.S. <br />RAI <br />RODRIGUEZ <br />ARCHITECTS <br />INCORPORATED <br />2121 PONCE DE LEON BLVD, STE, 1010 <br />CORAL GABLES, FL. 33134 <br />TEL: (305) 448-3373 <br />FAX: (305) 448-3374 <br />A A C ----- 1 0 0 9 9 <br />0 <br />LL- <br />z W <br />o z <br />o o Q0 <br />z <br />w 0 r <br />J <br />L.L. <br />J __j _ <br />U <br />Q w <br />L.L. m <br />0 <br />V) <br />w <br />0 <br />w <br />0 <br />M <br />L0 <br />w <br />a <br />a <br />Q <br />m <br />Q <br />0 <br />Q <br />REVISIONS: <br />cn <br />w <br />J <br />STRUCTURAL GENERAL NOTES <br />SCHEDULES AND DETAILS <br />SCALE INDICATED <br />CHECKED BY: <br />ISSUE DATE; <br />MAR <br />02/04/22 <br />DRAWN BY; <br />FPROJECT NO. <br />DMS <br />2154 <br />n2 -r 2r Ol <br />2e <br />L <br />I <br />NOTE: VALUES INDICATED ARE NET UPLIFT. <br />/-,4\UPLIFT DIAGRAM <br />SCALE: N.T.S. <br />RAI <br />RODRIGUEZ <br />ARCHITECTS <br />INCORPORATED <br />2121 PONCE DE LEON BLVD, STE, 1010 <br />CORAL GABLES, FL. 33134 <br />TEL: (305) 448-3373 <br />FAX: (305) 448-3374 <br />A A C ----- 1 0 0 9 9 <br />0 <br />LL- <br />z W <br />o z <br />o o Q0 <br />z <br />w 0 r <br />J <br />L.L. <br />J __j _ <br />U <br />Q w <br />L.L. m <br />0 <br />V) <br />w <br />0 <br />w <br />0 <br />M <br />L0 <br />w <br />a <br />a <br />Q <br />m <br />Q <br />0 <br />Q <br />REVISIONS: <br />cn <br />w <br />J <br />STRUCTURAL GENERAL NOTES <br />SCHEDULES AND DETAILS <br />SCALE INDICATED <br />CHECKED BY: <br />ISSUE DATE; <br />MAR <br />02/04/22 <br />DRAWN BY; <br />FPROJECT NO. <br />DMS <br />2154 <br />,/ D.D.A. ENGINEERS P.A. <br />CONSULTING ENGINEERS <br />4930 S.W. 74TH Court <br />Miami, Florida, 33155 <br />1 Phone: (305)666-07-1-1 <br />Fax:(305)666-5259 <br />" www.ddaeng.com <br />2022-42-B OF <br />53.01 <br />SHEETS <br />