<br />- M.. EXISTING
<br />LTG. ® 125X (42.2 x .1.23) 52:6kVA RCPTS: 1st 10kVA 0, 100X 1,0.0 kVA
<br />NEW WORK HVAC .® 100X' - (70.4.. x 1.0) _ ...O.OWA Remaining OVA ® 5OX . (0.O x 0.5) . = 0.0 OVA
<br />EQUIP ® 1.0076. (26.6 x ,1.:0) _ O.OWA TOTAL _ 159.8 I WA _> 192.3A
<br />LOAD CALCS:
<br />EXISTING .: LTG. O 125X (79.0 x 1:23) 08:SWA RCPTS: lot 10kVA ®100X _ 0.0 kVA
<br />NEW .WORK:..
<br />HVAC 0. 10076 (0..0 x 1.0) O.OWA Remaining O .507E .0 x m.5) _ ,0.0 WA
<br />EQUIP ® 10076 . (78.3 x 1.0) _ 78.310A TOTAL _ 177 1 kV A => 2111A
<br />Sigk
<br />8
<br />U
<br />Z.
<br />V)
<br />Nz .
<br />o
<br />J3 at
<br />Ca
<br />LOAD CALLS:
<br />- EXISTING
<br />LTG ®. 125X. (0.0 x 1.25). .O.,0WA RCPTS: 1st 1OWA ® 1008 10.0 kVA
<br />NEW.:WORK
<br />HNAC ® . 1 OOx (0.0 X. 1.0) _ O.OWA Remaining kVA 0 307E (35.5
<br />x '0.81 _ 1-1.8 kVA
<br />vEQUIP O 100X (0:0 x 1.0) O.OWA TOTAL = 28.0 kVA _> 77.6A
<br />PROVIDE 12 "SQ x 4" DEEP
<br />J -BOX FOR DOOR STRIKE
<br />TRANSFORMER AND CONTROL
<br />UNIT F_...
<br />% <, TO FIRE' ALARM
<br />CONTROL PAINEi I0
<br />R L
<br />EA -,,.
<br />4 SQ x 2 » DEEP 'J -BOX FOR �yLs U O ALARM
<br />DOOR OPEN DETECTOR, TYPICAL, _ .......................... y 314'C
<br />COORDINATE LOCATION W /DOOR 3/4 "C (TYP) 1 »C ,.__.. _. _ . _..._...._..,._ ... TC C;; Hl:r DOORS HARDWARE CONTRACTOR
<br />i
<br />CEILING
<br />COORDINATE i••- -- '
<br />EXACT LOCATION I I ( EXISTING,
<br />OF CONDUIT WITH I ACCESS ••
<br />DOOR CONTRACTOR. I i COI�TRO ° °- ° °-- EXISTING
<br />CONDUIT SHALL BE £ PANEL I NEW WORK
<br />ROUTED IN DOOR _ W /BACKUP {
<br />FRAME ON STRIKE+ I E+48"
<br />I Fzt?WI"R i
<br />SIDE. KP .w SUPPLY
<br />TYPICAL DOOR - I
<br />1
<br />I ELECTRICAL RM
<br />- _ ..,. ........ ........m FLOOR
<br />FOR ELECTRIC DOOR STRIKE UNIT STANDARD DOUBLE GANG BACK BOX
<br />(UNIT PROVIDED BY OTHERS), FOR CARD KEY OR SCANNER UNIT.
<br />COORDINATE LOCATION WITH (UNIT PROVIDED BY OTHERS). COORDINATE
<br />DOOR HARDWARE CONTRACTOR. LOCATION WITH DOOR HARDWARE CONTRACTOR.
<br />NOTE:
<br />CONTRACTOR SHALL PROVIDE EXACT SAME SCANNERS AS EXISTING
<br />AND ADD TO EXISTING CARD ACCESS SYSTEM PANEL WHICH IS ALREADY
<br />INTERFACED WITH THE EXISTING FIRE ALARM PANEL. NEW DOORS WITH
<br />NEW SCANNERS SHALL BE RELEASED UPON ACTIVATION OF THE FIRE
<br />ALARM PANEL.
<br />i SECURITY ACCESS RI5ER DIAGRAM
<br />E201 .NTS
<br />I OR 2 HOURS FIFE RATED THROUGH
<br />PENETRATION PIRESTOP FOR
<br />SINGLE METAL PIPE THROUGH
<br />GYPSUM WALLS USING
<br />PIRE- 94IELD
<br />P4RATIN6 ■ 1 t 2 HR.
<br />T41tATIN6 ■ O HR.
<br />UL N W051
<br />OI OR 2 - HOUR FIRE RATED GYPSUM WALLSOARD/STUD A9SEM BILY
<br />(ANGULAR SPACE RANGE, MIN. V4" MAX. 509
<br />OCONDUIT - 4' dim (OR SMALLEW EMT OR RI61D STEEL.
<br />OTREMGO N FIRE -9 WLD- MIN.in" THICKNESS OF SEALANT
<br />INSTALLED WITHIN OPENING W/ A MIN. OF
<br />1/4' CRONI AROUNV GROUND THE PENETRATION
<br />ITEM APPLIED FLUSH W/ BOTH SIDE OF
<br />KAU A99IS48LY.
<br />2 HOURS FIRE RATED *ROUSH
<br />PENETRATION FIRESTOP FOR
<br />MULTIPLE METAL PIPE THROUGH
<br />c- OwRETE WALLS usm
<br />FIRE -51 IELD OR FIRE-1DlIAL.
<br />P- RA71N6 - 1 i 2 HR.
<br />T -RHINE - I/2 W.
<br />KI012 ")
<br />0 WALL Assm -my - 5' THICK c4w,. W/ MAX. AREA of
<br />OPENIMIS $5.15 9% In.
<br />0 STEEL PIPE • 2• DHa. (OR SM AL ERJ SOK 5 OR HEAVIER
<br />CONDUIT - 2" d1c. (OR SMALI.L'W EMT.
<br />MAX. 5 PIPES OR CONDUITS.
<br />® A) STIES. SLEEVE - No. 50 MSG goly. SHEET PITTED WITHIN
<br />OPENING s SECURED TO BOTH SIDES
<br />OF WALL.
<br />51 PACKIWS HNITERIAL - MINA• THIC40455 CERAMIC FIBER
<br />INSULATION (6 PCP) MroTIoN FITTED
<br />W MIN. V2' THICKNe FIRE- SHIELD OR FIRE SEAL, WITH 1/4' GROM
<br />FORPIND APO" PENETRATION ITEMS.
<br />2 HOURS FIRE RATED THROUSH
<br />PENETRATION FIRESTOP FOR
<br />51NSI.E METAL PIPE THHIeOU6H
<br />GONG. FLOOR OR RK WALLS
<br />USING TREMSTOP ACRYLIC.
<br />F- RATHN6 a 2 HR.
<br />T- RATINS ■ O HR.
<br />UL * G JI20s
<br />WIN
<br />0
<br />MA
<br />i PRE -RATED CONCRETE K=RS OR IRK WALLS • Min. 4112'
<br />THNGK, NTH ANNUL.AR SPACE RANEE OF
<br />0" TO 1w
<br />2 CONDUIT - 4" dla. (OR 5MALIEW STL. CONDUIT OR EMT.
<br />5 TREMCO M FIRE 91 MIKV2' THICKNESS OF SEALANT
<br />INSTALLED WITHIN OPI NINS W/ A MIKOF
<br />114" CROM AROM ORO" THE ITEM APPLIED
<br />FLUSH W/ BOTH SIDE OF WALLS ASSEMBLY.
<br />4 TREMGO M TR"TiOP ACRYLIC - Min, 1/2' SEALANT APPLIED
<br />WITHIN AN US I A Min. V41 SEALANT
<br />APPLIED AT POINT CONTACT AT FLOOR
<br />SURFACE FOR FLOORS, OR DOTH SURPACES
<br />FOR WALLS.
<br />2 FIRESTOFFING DETAILS
<br />E201 NTS
<br />GENERAL ELECTRICAL NOTES
<br />1. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE 2005 EDITION
<br />OF THE NATIONAL ELECTRIC CODE, 2007 N.F.P.A. 72, 2006 N.F.P.A. 101, 2004 FLORIDA
<br />FIRE PREVENTION CODE, 2004 F.B.C., LOCAL CODES, ORDINANCES, INCLUDING ALL
<br />AMENDMENTS TO THE N.E.C. EQUIPMENT, WHERE APPLICABLE, WILL BE LISTED WITH THE
<br />UNDERWRITERS LABORATORIES, INC. QUALITY AND WORKMANSHIP ESTABLISHED BY DRAWINGS AND
<br />SPECIFICATIONS ARE NOT TO BE REDUCED BY THE ABOVE MENTIONED CODES.
<br />2. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND
<br />SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL
<br />BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT,
<br />OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN
<br />HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED.
<br />3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST -CLASS
<br />WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE OF
<br />THIS SYSTEM BY THE ENGINEER MUST BE A CONDITION OF THE SUB CONTRACT.
<br />4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE
<br />PROGRESS OF CONSTRUCTION.
<br />5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR PERIOD
<br />OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE.
<br />6. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE
<br />REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN
<br />DAMAGED THEREBY.
<br />7. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF
<br />PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
<br />8. CONTRACTOR TO PAY FOR ALL PERMIT FEES, INSPECTIONS AND TESTINGS.
<br />9. ALL WIRING SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED, MINIMUM WIRE SIZE SHALL
<br />BE #12 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE COPPER WITH
<br />THWN /THHN INSULATION. CONDUCTORS #10 AND SMALLER MAY BE SOLID; ALL THOSE #8
<br />AND LARGER TO BE STRANDED.
<br />10. ALL UNDERGROUND RACEWAYS SHALL BE MINIMUM 3/4 ", GALVANIZED RIGID STEEL CONDUIT OR
<br />SCHEDULE 40 PVC. ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES. RIGID STEEL
<br />SHALL ALSO BE USED WHEN CONDUIT IS EXPOSED TO EXTERIOR ENVIRONMENT SUCH AS EXTERIOR
<br />OF BUILDING OR WHERE IT IS EXPOSED AND SUBJECT TO DAMAGE, INSIDE OF BUILDING.
<br />11. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS
<br />IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER CLASSIFIED AREAS.
<br />ALL BOXES SHALL BE RECESSED (FLUSH) IN WALLS OR CEILINGS WHENEVER POSSIBLE.
<br />12. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE
<br />MANUFACTURER. CATALOG NUMBERS LISTED ARE LEVITON: HOWEVER, COMPARABLE DEVICES BY
<br />PASS & SEYMOUR, BRYANT, OR ARROW HART WILL BE ACCEPTED. COLOR OF DEVICES AND
<br />PLATES SHALL BE DICTATED BY ARCHITECT /OWNER.
<br />A. SWITCHES: LEVITON #CSB1 -201 OR EQUAL
<br />B. RECEPTACLES: LEVITON #BR20 -1 OR EQUAL
<br />C. COVER PLATES: SMOOTH PLASTIC
<br />NOTE: ALL OTHER REQUIRED DEVICES SHALL MATCH IN COLOR AND STYLE.
<br />13. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE
<br />CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL
<br />SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT TO BE PLACED
<br />IN PROPER WORKING ORDER.
<br />14. A SEPARATE, GREEN TYPE THWN COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG OF
<br />EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET
<br />BOX. DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND.
<br />A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND
<br />SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE
<br />GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250 -122 OF THE N.E.C.
<br />CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR.
<br />15. LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ENGINEER AT THE 11ME OF DESIGN.
<br />VERIFY ALL EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING.
<br />16. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. : THE CONTRACTOR
<br />IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS.
<br />17. ALL FLUORESCENT LIGHT FIXTURES SHALL HAVE IN LINE FUSING AND ELECTRONIC BALLASTS.
<br />(FUSING ONLY REQUIRED IN MIAMI DADE COUNTY)
<br />18. ALL PANELBOARD BREAKERS SHALL BE THE PRODUCT OF EXISTING PANELBOARD
<br />MANUFACTURER, THE SYSTEM DESIGN IS BASED ON SIEMENS; HOWEVER, COMPARABLE EQUIPMENT
<br />BY G.E. & SQUARE "D" ONLY WILL BE FIELD VERIFIED. TANDEM AND HALF- SPACE. CIRCUIT
<br />BREAKERS SHALL NOT BE USED.
<br />19. TYPEWRITTEN CIRCUIT INDEX SHALL BE AFFIXED TO INSIDE SURFACE OF EACH PANELBOARD
<br />DOOR, CLEARLY INDICATING AREA AND TYPE OF LOAD SERVED BY EACH BRANCH CIRCUIT
<br />PROTECTIVE DEVICE, INCLUDING SPARES. HAND PRINTED WILL NOT BE ACCEPTED.
<br />20. ENGRAVED, LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED
<br />ON ALL PANELS. PLATES SHALL BE AFFIXED TO FRONT OF PANELS, INDICATING
<br />PANEL NAME, VOLTAGE AND AMPERAGE.
<br />21. ALL UNDERGROUND PVC CONDUIT RUNS SHALL HAVE RIGID STEEL ELBOWS AND RIGID STEEL
<br />SECTIONS AT SLAB PENETRATIONS WHERE SUBJECT TO POSSIBLE DAMAGE.
<br />22. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY, EMT, RIGID
<br />OR GALVANIZED CONDUIT. MAXIMUM NUMBER OF 120V CIRCUITS ALLOWED IN A COMMON CONDUIT
<br />SHALL BE THREE (3). THE CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. REQUIREMENTS
<br />OF DERATING FOR CONDUCTOR AMPACITY AND CONDUIT FILL.
<br />23. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS:
<br />480V SYSTEM 208V SYSTEM PHASE SEQUENCE
<br />NEUTRAL - GREY NEUTRAL -WHITE A,B,C TOP TO BOTTOM,
<br />PHASE A - BROWN PHASE A - BLACK LEFT TO RIGHT,
<br />PHASE B - PURPLE PHASE B - RED FRONT TO BACK
<br />PHASE C - YELLOW PHASE C - BLUE
<br />GRD.CON - GREEN GRD.CON - GREEN
<br />24. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE THROUGH
<br />FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L ASSEMBLY
<br />STANDARDS.
<br />25. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH
<br />COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO
<br />BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. EVERY UNIT OF
<br />EQUIPMENT, DEVICE, CONDUIT AND WIRE IS TO BE MARKED WHEN INSTALLED. USE BEN TO
<br />INDICATE INSTALLATION AS SHOWN ON DRAVMNGS AND. USE $EQ TO INDICATE FIELD CHANGES.
<br />UPON COMPLETION OF WORK, THIS SET OF (CONTRACT DRAWINGS IS TO BE TURNED OVER TO,
<br />AND BECOME PROPERTY OF THE ELECTRICAL ENGINEER.
<br />26. CONTRACTOR SHALL PROVIDE ACCURATE AS -BUILT DRAWINGS AND EQUIPMENT OPERATION MANUALS
<br />TO THE BUILDING OWNER PRIOR TO FINAL ACCEPTANCE OR CLOSEOUT IN ACCORDANCE WITH
<br />F.B.C. 2004 EDITION, ARTICLE 13- 413.1.ABC.2
<br />27. ALL PANELBOARD FEEDERS SHALL BE SIZED NOT TO EXCEED 2% VOLTAGE DROP AND ALL
<br />BRANCH CIRCUITS SHALL BE SIZED NOT TO EXCEED 3% VOLTAGE DROP PER
<br />F.B.C. 2004 EDITION, ARTICLE 13- 413.1.ABC "1.
<br />28. LIGHTING CONTROL SHALL BE BASED UPON F.B.C. 2004 EDITION, ARTICLE 13- 415.1.ABC.1
<br />29. LIGHTING PERFORMANCE CALCULATIONS SHALL BE BASED UPON F.B.C. 2004 EDITION, ARTICLE
<br />13- 415.2.ABC.1 WHERE THE BLDG AREA METHOD PRESCRIBED IN 13- 415.2.C.1 SHALL BE USED.
<br />
|