ELECTRICAL NOTES <br />1. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE ADOPTED EDITION <br />OF THE NATIONAL ELECTRIC CODE, N.F.P.A., LOCAL CODES, ORDINANCES, INCLUDING ALL <br />AMENDMENTS TO THE N.E.C. EQUIPMENT, WHERE APPLICABLE, WILL BE LISTED WITH THE <br />UNDERWRITERS LABORATORIES, INC. QUALITY AND WORKMANSHIP ESTABLISHED BY DRAWINGS AND <br />SPECIFICATIONS ARE NOT TO BE REDUCED BY THE ABOVE MENTIONED CODES. <br />2. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND <br />SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL <br />BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT, <br />OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN <br />HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. <br />3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST -CLASS <br />WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE OF <br />THIS SYSTEM BY THE ENGINEER MUST BE A CONDITION OF THE SUB CONTRACT. <br />4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE <br />PROGRESS OF CONSTRUCTION. <br />5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR PERIOD <br />OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. <br />6. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE <br />REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN <br />DAMAGED THEREBY. <br />7. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF <br />PROPERTY DAMAGE FOR THE DURATION OF THE WORK. <br />8. CONTRACTOR TO PAY FOR ALL PERMITS, FEES INSPECTIONS AND TESTINGS. <br />9. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND <br />TELEPHONE COMPANIES. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL POWER AND <br />TELEPHONE COMPANIES PRIOR TO START OF CONSTRUCTION. <br />10. ALL WIRING SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED, MINIMUM WIRE SIZE SHALL <br />BE 12 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE COPPER WITH <br />THWN /THHN INSULATION. CONDUCTORS 10 AWG AND SMALLER MAY BE SOLID; ALL THOSE 8 AWG <br />AND LARGER TO BE STRANDED. <br />11. ALL UNDERGROUND RACEWAYS SHALL BE MINIMUM 3/4 ", GALVANIZED RIGID STEEL CONDUIT OR <br />SCHEDULE 40 PVC. ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES. WHERE RIGID STEEL <br />IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST RESISTANT BITUMASTIC <br />PAINT, COPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. RIGID STEEL <br />SHALL ALSO BE USED WHEN CONDUIT IS EXPOSED TO EXTERIOR ENVIRONMENT SUCH AS EXTERIOR <br />OF BUILDING OR WHERE IT IS EXPOSED AND SUBJECT TO DAMAGE, INSIDE OF BUILDING. <br />12. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK -MAKE, QUICK -BREAK TYPE. <br />ENCLOSURES SHALL BE AS REQUIRED BY N.E.C. AND LOCATION (WEATHERPROOF, EXPLOSION <br />PROOF, ETC.). ENGRAVED LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND <br />INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS. <br />13. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. FUSES SHALL BE THOSE <br />MANUFACTURED BY EITHER BUSSMAN OR LITTLEFUSE. THE CONTRACTOR SHALL FURNISH TO THE OWNER <br />ONE SPARE FUSE FOR EACH SIZE AND TYPE OF FUSE INSTALLED. FUSES 600 AMPS OR LESS SHALL <br />BE CLASS RK1, TYPICAL UNLESS OTHERWISE NOTED. FUSES OVER 600 AMPS SHALL BE CLASS L. <br />14. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE <br />CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL <br />SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT BE PLACED IN <br />PROPER WORKING ORDER. <br />15. _A SEPARATE, GREEN TYPE THWN COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG OF <br />EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET <br />BOX. DEVICE MOUNTING SCREWS 'SHALL NOT BE CONSIDERED AN AP'RROVEO GROUND. <br />A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RA _ II'...;r r <br />SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE <br />GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250 -122 OF THE N.E.C. <br />CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR. <br />16. LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ENGINEER AT THE TIME OF DESIGN. <br />VERIFY ALL EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING. <br />17. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR <br />IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS. <br />18. ALL SWITCHGEAR, PANELS, STARTERS, CONTACTORS ETC., SHALL BE THE PRODUCT OF A SINGLE <br />MANUFACTURER, THE SYSTEM DESIGN IS BASED ON SQUARE "D "; HOWEVER, COMPARABLE EQUIPMENT <br />BY G.E. & SIEMENS ONLY WILL BE ACCEPTABLE. TANDEM AND HALF -SPACE CIRCUIT BREAKERS <br />SHALL NOT BE USED. <br />19. ALL UNDERGROUND PVC CONDUIT RUNS SHALL HAVE RIGID STEEL ELBOWS AND RIGID STEEL <br />SECTIONS AT SLAB PENETRATIONS WHERE SUBJECT TO POSSIBLE DAMAGE. WHERE RIGID STEEL <br />IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST- RESISTANT BITUMASTIC <br />PAINT, COPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. <br />20. THE ELECTRICAL CONTRACTOR SHALL MEET AND COORDINATE WITH THE LOCAL POWER COMPANY <br />AT THE SITE PRIOR TO CONSTRUCTION. AT THAT TIME, THE CONTRACTOR SHALL COORDINATE <br />ALL RELATED WORK WITH THE UTILITY COMPANY'S RESPONSIBILITIES TO 'MEET THE OWNERS SCHED. <br />21. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY, EMT, IMC, RIGID <br />GALVANIZED CONDUIT OR SCHEDULE 40 P.V.C. THERE SHALL BE NO TYPE 'NM', ELECTRICAL <br />NON- METALLIC TUBING, & FLEXIBLE METAL CONDUIT USED FOR BRANCH CIRCUITING. MAXIMUM <br />NUMBER OF 120V CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE SIX (6). "MC" TYPE CABLE <br />SHALL NOT BE USED AS HOME RUNS. THE CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. <br />REQUIREMENTS OF DERATING FOR CONDUCTOR AMPACITY AND CONDUIT FILL. <br />22. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: <br />208V SYSTEM <br />240V (HIGH LEG) <br />SYSTEM <br />480V SYSTEM <br />NEUTRAL - <br />WHITE <br />NEUTRAL <br />- WHITE <br />NEUTRAL <br />- WHITE /STRIPE <br />PHASE A - <br />BLACK <br />PHASE A <br />- BLACK <br />PHASE A <br />-BROWN <br />PHASE B - <br />RED <br />PHASE B <br />- ORANGE PHASE B <br />- PURPLE <br />PHASE C - <br />BLUE <br />PHASE C <br />- BLUE <br />PHASE C <br />- YELLOW <br />GRD.CON - <br />GREEN <br />GRD.CON - <br />GREEN <br />GRD.CON <br />- GREEN <br />23. CONTRACTOR <br />SHALL <br />BE RESPONSIBLE FOR <br />SEALING ALL CONDUIT <br />PENETRATIONS MADE THROUGH <br />FIRE RATED <br />WALLS, <br />CEILINGS, SLABS, ETC. <br />PENETRATION <br />SEALS SHALL BE PER U.L. ASSEMBLY <br />STANDARDS. <br />4 <br />6 <br />UCIHTNG <br />=2 <br />24, CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH <br />COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO <br />BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. EVERY UNIT OF <br />EQUIPMENT, DEVICE, CONDUIT AND WIRE IS TO MARKED WHEN INSTALLED. USE OM TO <br />INDICATE INSTALLATION AS SHOWN ON DRAWINGS AND USE aM TO INDICATE FIELD CHANGES. <br />UPON COMPLETION OF WORK, THIS SET OF CONTRACT DRAWINGS IS TO BE TURNED OVER TO, <br />AND BECOME PROPERTY OF THE ELECTRICAL ENGINEER. <br />25. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN THEIR OPINION FINDS OMISSIONS OR <br />ERRORS ON ELECTRICAL DOCUMENTS, IT IS THEIR RESPONSIBILITY TO BRING THIS TO THE <br />ATTENTION OF THE ELECTRICAL ENGINEER IMMEDIATELY. IF ELECTRICAL CONTRACTOR PROCEEDS <br />WITH &ff CHANGES TO THE CONTRACT DOCUMENTS, WITHOUT WRITTEN PRIOR APPROVAL FROM <br />THE ELECTRICAL ENGINEER, CONTRACTOR WILL NOT BE COMPENSATED. <br />PANEL SCFEDUL.E-" Rr EXISTM <br />Rded Vd bp: . 0/t1101V 1PHAW Mwwbdwo: of MowMln6: awfusi <br />RNNATRPC(00b" am SPACES: 12 , As -AR: REiTROOMBUILDNI• Typ: NMI <br />Edo: MLA PNI" NOL QY3A0 A.I.O. 19 KAIC <br />DESIGNED <br />DATE <br />PANEL SCHEDULE A <br />RMN VoNatpi: 01t "w WHO= <br />RMd AWN (ICY b" WW TH" SPAOr: <br />Odic 2M <br />RVA <br />EXIS'r <br />88MMCOMIro: il■MENS <br />Loaoia:: PARK( NORTH $08) <br />Proloot Na t!6%i1.08 <br />WA <br />MaNdaS: <br />Typo: <br />A.I.C. <br />itEhOe <br />NL'MA4X <br />n Km <br />GFAW 0000MOTM <br />aim <br />MIiIDOIIa <br />ILCPT <br />am. La1D <br />Mom <br />PH <br />rAff <br />C:W. UM <br />MOTOR <br />AWWOM <br />0". <br />ORMI 01II0NA710N <br />10tA <br />1 <br />LCIHTNG <br />20x2 <br />lava <br />IWMA 1 <br />0.76 <br />MaM: <br />A <br />MCB <br />0.67 <br />prapd No. VIEWS <br />10•lrr <br />2D12 <br />UafrNG <br />2 <br />3 <br />0.78 <br />B <br />MfA <br />a67 <br />4 <br />6 <br />UCIHTNG <br />=2 <br />10.112" <br />W.P <br />0.83 <br />RCPT <br />A <br />1:60 <br />PH <br />MW <br />12 Vr <br />=I <br />RECEPTACLE LOAD <br />6 <br />7 <br />1 <br />0.63 <br />RESTROOM BULDM <br />ANEL <br />B <br />1.60 <br />0L0D <br />1.20 <br />121/7' <br />=I <br />RECEPTACLE LOAD <br />i <br />! <br />UC*ffm <br />02 <br />10.1re <br />2 <br />0.63 <br />0.00 <br />A <br />1.60 <br />B <br />an <br />12117' <br />20M <br />RECEPTACLE LOAD <br />110 <br />11 <br />S -0" <br />1 <br />0.83 <br />am <br />B <br />1.80 <br />A <br />848 <br />12-IW <br />2112 <br />RECEPTACLE LOAD <br />12 <br />13 <br />LK*ffNG <br />=2 <br />1M17 <br />1 <br />ale <br />A. <br />1.80 <br />B <br />! <br />14 <br />16 <br />M' <br />M16 <br />SPACE <br />t <br />! <br />SPACE <br />SPACE <br />1i <br />17 <br />Uc*ff i <br />2wl <br />104W <br />0.20 <br />SPACE <br />A <br />11 <br />SPACE <br />0.80 <br />12 Wr <br />20N <br />TRIER 1 <br />1t <br />B <br />SIPACE <br />an <br />B <br />SPACE. <br />B <br />SUF AL CONNECTED LOAD: <br />aeo <br />12-Vr <br />wn <br />TIMER 2 <br />3! <br />211 <br />WA" FOUNTAIN <br />: SUBTOTAL CONNECTED LOAD <br />as <br />CONNECTED LOAD PHASE A: <br />0.80 <br />Al. <br />. 000 <br />1.2D <br />286 <br />note 1 <br />10012 <br />RESiROOM PANEL <br />22 <br />23 <br />BUNTER PUMP <br />02 <br />10.112" <br />8.8 <br />note 2 <br />1.44 <br />81 <br />0.00 <br />0.00 <br />676 <br />LN"M <br />W <br />26 <br />1.2 <br />W63 <br />1.44 <br />A <br />TOTAL OONSECTED LOAD: <br />9.8 <br />SPRINKLER CONTROL. PANEL <br />0t <br />27 <br />SIPARE <br />RECEPT. CONiEOM LOAD: <br />1.20 <br />B <br />nob 6 <br />phg% at aaaaoLd <br />SPACE <br />21 <br />Sol <br />SIPACE <br />066 1 <br />TOTAL COMPUTED LOAD: <br />10 KVA <br />nobs <br />tho nv lohoad:obd <br />A <br />0.0 <br />: SUBT'OTAL CONNECTED WAD <br />OONECTED LOAD PH ASE'A: <br />SPACE <br />36 <br />31 <br />hsd ood&cw <br />1.3 <br />nob 1 <br />vs*=x O C.P.D. ift �nnpYb <br />OONECTE6 LOAD PHASE S: <br />an <br />t ii <br />a.6! <br />a• Rq■t <br />BLO <br />NBTII PANBL B <br />7HDaq <br />32 <br />33 <br />a6D <br />Lil <br />a 66 <br />34 <br />OONEC= CONTINUOUS LOAD 010016: <br />*UE1W&OONNEC=LOAMj <br />nob 3 <br />in . Aw on fid bad <br />ai <br />I aS <br />ss <br />6.2 <br />9.1 <br />7.6 <br />616 <br />: SUB'TOTAL CONNECTED LOAD <br />nob 4 <br />CkF.C.L type ohaCT<k*dw <br />OONECTW LARD PHASE A: <br />OONECTED LOAD PHASE B: <br />TM& 0ONN SOM WAR <br />RECBPT. CXX NBCTBD LCIA[k <br />146 <br />17.7 <br />311 <br />a1 <br />RECEPL OONNEMED LOAD: <br />0.0 <br />CONTINUOUS i LARGEST U07M 0 26%: <br />CONNECT MOTOR LOADS Q 100%: <br />CONNECTED OCNTNUOUS LOAD 0100%: <br />RECEPTACLE COMPUTED LOM <br />TOTAL COMPUTED LOAD: <br />3.3 <br />13.3 <br />13.3 <br />8.1 <br />38 <br />1N <br />KVA <br />AMPS <br />nob 1 <br />nob 2 <br />nob 3 <br />n04 <br />rata 6 <br />rob a <br />rota 7 <br />vw* max MC.F.D. w& namepbM <br />b*" okonl bnkw <br />n0n.00RaRCrd bad <br />QF.C.L typo okoul6naloet <br />phdo Dot o0dnabd <br />time swloh oo*cbd <br />nw&@do had a0daobr <br />PANEL SCFEDUL.E-" Rr EXISTM <br />Rded Vd bp: . 0/t1101V 1PHAW Mwwbdwo: of MowMln6: awfusi <br />RNNATRPC(00b" am SPACES: 12 , As -AR: REiTROOMBUILDNI• Typ: NMI <br />Edo: MLA PNI" NOL QY3A0 A.I.O. 19 KAIC <br />DESIGNED <br />DATE <br />PANEL. SCHI DULE "R1" <br />Cddn, `.GQ{"1{� w 6 ��M I1�:. <br />TOWN CENTER PARK <br />EXISTW <br />APPROVED '� W. SCALE SHEET <br />FLORIDA <br />• Swv <br />Tbbd VdbW. <br />010!12611 <br />1PHAW <br />T.W. <br />OCT. 2008 <br />MmdYdwm of <br />Men": <br />Howdy: <br />surfs" <br />CHECKED <br />Rd d ARIA: (Go b" <br />Rath AMC (On 6" <br />10tA <br />SPAIN: <br />12 <br />Looaiae: EAST SIDE OF RESTROOM <br />rps: <br />IWMA 1 <br />MaM: <br />Maly: <br />MCB <br />prapd No. VIEWS <br />prof" Na we" <br />A.LC. <br />A.LO. <br />1• KMC <br />KVA <br />MfA <br />KVA <br />OWN= OBINIM7fON <br />OWAW00N MTIDN <br />W.P <br />AwWnm <br />RCPT <br />mw Caro <br />umm <br />PH <br />MW <br />MW Cato <br />-MN <br />AvMall:oMQ <br />WA <br />OrROLN1'DBDNSIM710N <br />1 <br />1 <br />RESTROOM BULDM <br />ANEL <br />5012 <br />3-1412 <br />0L0D <br />1.20 <br />2.88 <br />A <br />a13 <br />wr <br />lllt <br />3012 <br />E WTM CIRCUIT <br />tom <br />2 <br />3 <br />0.00 <br />0.00 <br />6.78 <br />B <br />an <br />4 <br />4 <br />6 <br />SPACE <br />S -0" <br />1 <br />am <br />A <br />A <br />848 <br />M" <br />IBIS <br />NEW PARK <br />LMMIi <br />SPACE <br />6 <br />7 <br />SPACE <br />1 <br />31 <br />a40 <br />B <br />! <br />NEN BOU ARD <br />02 <br />M' <br />SPACE <br />t <br />! <br />SPACE <br />SPAIN <br />A <br />SPACE <br />If <br />11 <br />SPACE <br />11 <br />LNNTi <br />B <br />an <br />B <br />SPACE. <br />12 <br />SUF AL CONNECTED LOAD: <br />0.0 <br />1! <br />a8 <br />13 <br />NE1Y BOLLARD <br />202 <br />&S <br />: SUBTOTAL CONNECTED LOAD <br />as <br />CONNECTED LOAD PHASE A: <br />41 <br />OONT1N K)US & LARGEST MOTOR 0 26%: <br />0.3 <br />note 1 <br />,,m, muL O.CLP.D. w6 swo pbb <br />CONNECTED LOAD PHASE S <br />6.8 <br />CONNECT MOTOR LOADS Q 100%: <br />8.8 <br />note 2 <br />bok*b drool brnbr <br />191 <br />LN"M <br />CONNECTED OONTNLKXM LOAD 0100%: <br />1.2 <br />W63 <br />noo-oaog en -Ind <br />B <br />TOTAL OONSECTED LOAD: <br />9.8 <br />RECEPTACLE COMPUTED WAD: <br />0.0 <br />rots 4 <br />QF C.L We *Ovk bedw <br />RECEPT. CONiEOM LOAD: <br />0.0 <br />A <br />nob 6 <br />phg% at aaaaoLd <br />SPACE <br />1t <br />SLE70T'ALCCONEC7EO LOAD <br />066 1 <br />TOTAL COMPUTED LOAD: <br />10 KVA <br />nobs <br />tho nv lohoad:obd <br />1.3 <br />0.0 <br />: SUBT'OTAL CONNECTED WAD <br />OONECTED LOAD PH ASE'A: <br />2.8 <br />42 AMPS <br />rob7 <br />hsd ood&cw <br />1.3 <br />PANEL SCFEDUL.E-" Rr EXISTM <br />Rded Vd bp: . 0/t1101V 1PHAW Mwwbdwo: of MowMln6: awfusi <br />RNNATRPC(00b" am SPACES: 12 , As -AR: REiTROOMBUILDNI• Typ: NMI <br />Edo: MLA PNI" NOL QY3A0 A.I.O. 19 KAIC <br />DESIGNED <br />DATE <br />PAIN. SCHEDULE B <br />Cddn, `.GQ{"1{� w 6 ��M I1�:. <br />TOWN CENTER PARK <br />NEW <br />APPROVED '� W. SCALE SHEET <br />FLORIDA <br />• Swv <br />R -1 -V~: <br />01tPIWV <br />1PHAW <br />T.W. <br />OCT. 2008 <br />100010 hm 4111BN"1A308AL1SDOTS <br />Men": <br />swkm <br />No E102 <br />06 -5723 <br />CHECKED <br />Rd d ARIA: (Go b" <br />100A <br />SFAM: <br />1S <br />LOaa -1 : PARK (NORTH SIDE) <br />TIM: <br />1101MA43( <br />Dais . ot. Authorization 514 <br />MaM: <br />MLA <br />prapd No. VIEWS <br />A.LC. <br />n KAIC <br />KVA <br />ANA <br />OWN= OBINIM7fON <br />CLC P. <br />RCPT <br />COW. LOAD <br />MUM <br />PH <br />W" <br />cow WD <br />MOTOR <br />MMM <br />acp <br />ONww DBTLIM1117MN1 <br />1 <br />NEDII BOLLARD <br />LIGHTS <br />2812 <br />M' <br />LIE <br />A <br />a13 <br />wr <br />lllt <br />NEW PARK <br />ume <br />2 <br />3 <br />an <br />B <br />an <br />4 <br />6 <br />NEN BOLLARD <br />!Et <br />S -0" <br />1 <br />am <br />A <br />848 <br />M" <br />IBIS <br />NEW PARK <br />LMMIi <br />6 <br />7 <br />91A <br />1 <br />31 <br />a40 <br />• <br />! <br />NEN BOU ARD <br />02 <br />M' <br />an <br />A <br />SPAIN <br />» <br />11 <br />LNNTi <br />an <br />B <br />SPAEB <br />12 <br />13 <br />NE1Y BOLLARD <br />202 <br />M" <br />as <br />A <br />SPATES <br />14 <br />191 <br />LN"M <br />a4I <br />B <br />SPADE Ile <br />17 <br />SPARE <br />A <br />SPACE <br />1t <br />SLE70T'ALCCONEC7EO LOAD <br />066 1 <br />3.S 1 <br />0.6 <br />ae <br />1.3 <br />0.0 <br />: SUBT'OTAL CONNECTED WAD <br />OONECTED LOAD PH ASE'A: <br />2.8 <br />OONTPIUOUS & LARGEST M07M Q 2616: <br />1.3 <br />nob 1 <br />vs*=x O C.P.D. ift �nnpYb <br />OONECTE6 LOAD PHASE S: <br />28 <br />CONNECT MOTOR WADS 010016: <br />0.0 <br />nob 2 <br />bdW6 cku* b sd wT <br />OONEC= CONTINUOUS LOAD 010016: <br />6.2 <br />nob 3 <br />in . Aw on fid bad <br />TOTAL O6NN1WM LOAD. <br />6.2 <br />RECEPTACLE COMPUTED LOAD: <br />0.0 <br />nob 4 <br />CkF.C.L type ohaCT<k*dw <br />RECEPL OONNEMED LOAD: <br />0.0 <br />nob 6 <br />phdo oe1 oodrobbd <br />TOTAL COMPUTED LOAD: <br />7 KVA <br />nee <br />dwnrbhmkobd <br />27 AMPS <br />nob? <br />hsd oodwww <br />PANEL SCFEDUL.E-" Rr EXISTM <br />Rded Vd bp: . 0/t1101V 1PHAW Mwwbdwo: of MowMln6: awfusi <br />RNNATRPC(00b" am SPACES: 12 , As -AR: REiTROOMBUILDNI• Typ: NMI <br />Edo: MLA PNI" NOL QY3A0 A.I.O. 19 KAIC <br />DESIGNED <br />DATE <br />T.W. <br />OCT. 2008 <br />Cddn, `.GQ{"1{� w 6 ��M I1�:. <br />TOWN CENTER PARK <br />ELECTRICAL RISER <br />APPROVED '� W. SCALE SHEET <br />FLORIDA <br />• Swv <br />LICENSE N0. 20957 <br />N . T. S <br />DRAWN <br />DATE <br />T.W. <br />OCT. 2008 <br />1806 Eller Drive, Suite 600 <br />Fort Lauderdale, Florida 93316 <br />CITY OF SUNNY ISLES BEACH <br />AND°`)E� <br />No E102 <br />06 -5723 <br />CHECKED <br />R.W.R <br />;Phone: 984.921.7781 Fax 954.921.8807 <br />0 <br />FLORIDA <br />PANEL SCHEDULES <br />CLAD FILE <br />NO DATE RLMSKiN BY NO DATE REVISK1Nl By DATE <br />OCT. 2008 <br />Dais . ot. Authorization 514 <br />DATE OF <br />