HomeMy WebLinkAboutSpecificationsRequest For Proposal #04 -04 -01 For a Category 6 Structured Cabling System At Sunny Isles Government Center Sunny Isles Beach, FL BID PACKAGE Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 1 INTRODUCTION ..................................................................................................... ............................... 1 -1 1.1 General Background ........................................................................................ ............................... 1 -1 1.2 Terms and Conditions of Bids .......................................................................... ............................... 1 -1 1.3 Instructions to the Bidder ................................................................................. ............................... 1 -2 1.4 Rights of the Purchaser .................................................................................... ............................... 1 -2 1.5 Schedule of Events .......................................................................................... ............................... 1 -2 2 QUALITY ASSURANCE .......................................................................................... ............................... 2 -1 2.1 Contractor Qualifications .................................................................................. ............................... 2 -1 2.2 Required Contractor Training ........................................................................... ............................... 2 -1 2.3 Contractor Responsibility ................................................................................. ............................... 2 -1 2.4 Manufacturer Quality & Product Substitutions ................................................. ............................... 2 -1 3 INDUSTRY REQUIREMENTS 3 -1 ................................................................................ ............................... 4 GENERAL REQUIREMENTS ................................................................................. ............................... 4 -1 5 SCOPE OF WORK .................................................................................................. ............................... 5 -2 5.1 Copper Backbone Cabling ............................. ............................... 5.2 Category 6 Horizontal Cabling ....................... ............................... 5.3 Closet Termination ......................................... ............................... 5.4 Work area ...................................................... ............................... 5.5 Fiber backbone .............................................. ............................... 6 BALANCED TWISTED -PAIR PRODUCT SPECIFICATIONS ............. 6.1 Outlets ............................................................ ............................... 6.2 Patch cords .................................................... ............................... 6.3 Patch panels .................................................. ............................... 6.4 Connecting Blocks ......................................... ............................... 6.5 Cable .............................................................. ............................... 7 OPTICAL FIBER PRODUCT SPECIFICATIONS . ............................... 7.1 Outlets /Adapters ............................................ ............................... 7.2 Connectors ..................................................... ............................... 7.3 Patch Cords / Pigtails ....................................... ............................... 7.4 Enclosures ..................................................... ............................... 7.5 Cable .............................................................. ............................... 8 MOUNTING OPTIONS .......................................... ............................... 8.1 Faceplates ...................................................... ............................... 8.2 Racks ............................................................. ............................... 9 SYSTEM DESIGN REQUIREMENTS ................... ............................... 9.1 Horizontal Cabling .......................................... ............................... 9.2 Backbone Cabling .......................................... ............................... 9.2.1 Intrabuilding Cabling ............................... ............................... 9.2.2 Interbuilding Cabling ............................... ............................... 10 INSTALLATION ................................................... ............................... 10.1 Site Survey ................................................... ............................... 10.2 Physical Installation ...................................... ............................... 10.2.1 Cable Pathways .................................... ............................... 10.2.2 Intrabuilding Cable Routing .................. ............................... 10.2.3 Horizontal Cable Routing ...................... ............................... 10.2.4 Work Area Termination ........................ ............................... 10.2.5 Pulling Tension ..................................... ............................... 10.2.6 Bend Radius ......................................... ............................... 10.2.7 Slack ..................................................... ............................... 10.2.8 Cable Tie Wraps .................................. ............................... 10.2.9 Grounding ............................................. ............................... 10.2.10 Fire protection .................................... ............................... 10.2.11 Workmanship ..................................... ............................... 11 TESTING .............................................................. ............................... 11.1 Copper Testing .............................................. ............................... 11.2 Fiber Optic Testing ........................................ ............................... 12 ADMINISTRATION & DOCUMENTATION ................ ............................... 5 -2 ................ ............................... 5 -2 ................ ............................... 5 -2 ................ ............................... 5 -2 ................ ............................... 5 -2 ................ ............................... 6 -3 ................ ............................... 6 -3 ................ ............................... 6 -3 ................ ............................... 6 -3 ................ ............................... 6 -3 ................ ............................... 6 -3 7 -A ................ ............................... 12.1 Labeling ............................................................... ............................... ............ 7 -4 ............ 7 -4 ............ 7 -4 ............ 7 -4 ............ 7 -4 ............ 8 -5 ............ 8 -5 ............ 8 -5 ........ ............................... 9 -1 ........ ............................... 9 -1 ........ ............................... 9 -1 ........ ............................... 9 -1 ........ ............................... 9 -1 ...... ............................... 10 -2 ...... ............................... 10 -2 ...... ............................... 10 -2 ..... ............................... 10 -2 ..... ............................... 10 -2 ..... ............................... 10 -2 ..... ............................... 10 -3 ..... ............................... 10 -3 ..... ............................... 10 -4 ..... ............................... 10 -4 ..... ............................... 10 -4 ..... ............................... 10 -4 ..... ............................... 10 -4 ..... ............................... 10 -4 ..... ............................... 11 -1 ..... ............................... 11 -1 ..... ............................... 11 -1 ..... ............................... 12 -1 ..... ............................... 12 -1 Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 12.2 Drawings ...................................................................................................... ............................... 12 -1 12.3 Records ........................................................................................................ ............................... 12 -1 12.4 Reports ......................................................................................................... ............................... 12 -1 13 WARRANTY ............................................................................................................. ............................... 2 13.1 System Warranty ............................................................................................... ............................... 2 13.2 Product Warranty .............................................................................................. ............................... 2 13.3 Applications Supported ..................................................................................... ............................... 2 14 ATTACHMENTS ....................................................................................................... ............................... 3 14.1 Riser Diagram ................................................................................................... ............................... 3 15 INSURANCE REQUIREMENT ............................................................................... ............................... 23 Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 1 INTRODUCTION 1.1 GENERAL BACKGROUND This document is issued as a Request for Proposal ( "RFP ") for the supply and installation of a structured telecommunications cabling system for the Sunny Isles Beach Government Center. The structured cabling system will support voice, data, and imaging applications within the facility located at 18070 Collins Avenue, Sunny Isles Beach, FL 33160. This document describes the system requirements to be met in the proposals of the telecommunications cabling vendors to secure under contract all materials, design engineering, installation, and supervision and training services for the structured cabling system. 1.2 TERMS AND CONDITIONS OF BIDS This is an invitation to submit a bid based on the materials, systems and equipment described in this document. All bids must be submitted in accordance with the specifications and information contained herein, as well as with any addenda, if required, issued by the purchaser. It is the intent of the Drawings and Specifications to provide a complete workable telecommunication cabling system ready for the Owner's use. Any item not specifically shown on the Drawings or called for in the Specification, but normally required for a complete system, are to be considered a part of the contract. Consideration other than cost alone will be used in making the determination of the successful contractor. These factors will include financial stability, availability, design support, project management and field supervision. The Manufacturers and Products specified in the document are to be used. No substitutions of components specifically referenced will be allowed, without prior written customer consent after submittal review. The City reserves the right in it's sole and absolute discretion to reject any and all qualifiers, to cancel and /or withdraw the RFP at any time. The City reserves the right to award any contract to any respondee which it deems to offer the best overall service and be the most responsible responsive bidder, thereby the City is not bound to award any contract based solely on the lowest quoted price and no contract is created until it is signed with the approval of the City Commission. The City, in it's sole and absolute discretion, also reserves the right to negotiate separately with competing firms as it deems to be in the best interest of the City and as permitted by law. If only one responsive qualifier for commodity or contractual service is received, in response to the solicitation, an award may be made to the single qualifier, if the City Manager finds the price submitted is fair and reasonable, and that other prospective bidders had reasonable opportunity to respond, or there is not adequate time for re- solicitation. Further, the City Manager reserves the right, if it is in the best interests of the City,to negotiate with the sole bidder for the best terms, conditions, and price. The City Manager shall document the reasons that such action is in the best interests of the City. Otherwise, the qualification may be rejected and: ■ New qualifiers may be solicited; and /or ■ The sole qualifier may be rejected. The respondee is responsible for paying any and all taxes associated with the agreement. Section 287.133, Florida Statutes, provides that a person or affiliate, as defined in that section, who has been placed on the convicted vendor list following the conviction for a public entity crime may not submit a bid on a contract with a public entity for any contract for construction or repair of a public building or a public work, may not submit bids on leases of real property to a public entity, may not be awarded to perform work as a contractor, supplier, subcontractor, or consultant under a contract with any public entity, and may not transact business with any public entity in excess of the threshold of the amount provided in section 287.017 for CATEGORY TWO ($25,000) for a period of 36 months from the date of being placed on the convicted vendor list. Any such person or affiliate convicted of a public entity crime shall provide written notice of such conviction. Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 1.3 INSTRUCTIONS TO THE BIDDER Bids shall be valid for 90 days. The Bidder shall consider the nature and amount of work to be done as well as the difficulties involved in its proper execution. No bid will be accepted by any contractor who did not attend the scheduled mandatory site survey, unless this requirement is waived by the City. The bid shall include all costs deemed necessary to cover all contingencies essential to the installation of the specified system. Total cost for installation materials, labor project management, permit fees, taxes and other miscellaneous items must be listed separately. A complete materials list, including description, manufacturer, part number, quantity, unit price and total price must also be included. All products and materials shall be new, clean, free of defects and free of damage and corrosion. Where discrepancies are found during the bid process, the most stringent requirements must be included in the bid. Any cost encountered, which is not specifically itemized in the bid, shall not be incurred unless specifically agreed upon, in writing. No additional compensation will be allowed for extra work incurred on the part of the Contractor due to the contractor's failure to notice any existing condition, which may cause the additional labor. Bid responses shall be concise following the format and numbering of this specification. Items not requiring responses shall be acknowledged by the bidder as being understood. Bidders must notify the Purchaser as soon as detected any omissions or errors in the specification so corrective addenda may be issued. Such notification must be received by the Purchaser at least (10) days prior to the date for receipt of bids. Sealed bids will be accepted by the City Clerk at City Hall (17070 Collins Avenue Suite 250, Sunny Isles Beach, FL 33160) by the deadline listed in section 1.5 below. Bids received after the deadline will be returned unopened. Inquiries and requests for clarifications should be submitted to Derrick Arias, IT Director, in writing at 17070 Collins Avenue, Suite 250, Sunny Isles Beach, FL 33160 by the deadline listed in section 1.5 below. 1.4 RIGHTS OF THE PURCHASER The Purchaser reserves the right to accept any bid or, at its sole discretion, reject any or all bids for whatever reason it deems appropriate. The Purchaser reserves the right to purchase ALL or PART of the cabling materials and hardware needed for the project. Receipt of a bid response does not obligate the Purchaser to pay any expenses incurred by the bidder in preparation of the bid response or obligate the Purchaser in any other respect. The Purchaser reserves the right to modify the specifications contained in the Request for Quote at any time during the bidding period. Only changes issued as an addendum will be binding upon the Purchaser. No verbal instructions or interpretations of requirements shall be accepted. 1.5 SCHEDULE OF EVENTS The schedule below indicates the critical dates that must be satisfied by the Contractor. The Contractor must staff its work crews appropriately to meet the required dates of completion. The Contractor shall also have staff available to provide coverage during the cut over period of ( 2) days. ■ RFP issue 4/12/2004 ■ Pre -bid conference 4/26/2004 ■ Proposal due 5/3/2004 ■ Contract Award 5/20/2004 Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 2 QUALITY ASSURANCE 2.1 CONTRACTOR QUALIFICATIONS The Contractor shall at a minimum possess the following qualifications: Be in business a minimum of five (5) years. Contractor shall demonstrate satisfaction of sound financial condition and can be adequately bonded and insured if the project deems necessary. Possess those licenses /permits required to perform telecommunications installations in the specified jurisdiction. Personnel knowledgeable in local, state, and national codes and regulations. All work shall comply with the latest revision of the codes or regulations. When conflict exists between local or national codes or regulations, the most stringent codes or regulations shall be followed. Must possess current liability insurance certificates. It is preferable that contractor be registered with BICSI and have at least one RCDD on staff. Must have personnel fluent in the use of Computer Aided Design and possess and operate CAD software using .DWG or .DXF format. 2.2 REQUIRED CONTRACTOR TRAINING The Contractor shall be fully conversant and capable in the cabling of low voltage applications such as, but not limited to data, voice and imaging network systems. The Contractor shall at a minimum possess the following qualifications: Personnel trained and certified in the design of Category 6 Cabling systems. Personnel trained and certified to install the Category 6 Cabling systems. Provide references of the type of installation provide in this specification. Personnel trained and certified in fiber optic cabling, splicing, termination and testing techniques. Personnel must have experience using a light meter and OTDR. Personnel trained in the installation of pathways and support for housing horizontal and backbone cabling. 2.3 CONTRACTOR RESPONSIBILITY Contractor shall be obligated to exercise the highest standard of care in performing it's obligations as defined in this request for proposal. Contractor acknowledges that The City of Sunny Isles Beach will rely on contractor's expertise, ability and knowledge of the system being proposed and shall be obligated to exercise the highest of standard care in performing it's obligation as defined in the following Scope of Work. 2.4 MANUFACTURER QUALITY & PRODUCT SUBSTITUTIONS All telecommunications connecting hardware and cable must be made by an ISO 9001 Certified Manufacturer. All products must meet the technical requirements listed in sections 6 -8. Any products not meeting these requirements will not be considered. Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 3 INDUSTRY REQUIREMENTS The following installation, documentation, component and system industry specifications shall be met orexceeded: ■ ANSI /TIA/EIA- 568 -B.1 and addenda "Commercial Building Telecommunications Cabling Standard - Part 1: General Requirements" • ANSI /TIA/EIA- 568 -13.2 and addenda "Commercial Building Telecommunications Cabling Standard - Part 2: Balanced Twisted - Pair" • ANSI /TIA/EIA- 568 -B.3 and addenda "Commercial Building Telecommunications Cabling Standard - Part 3: Optical Fiber Cabling and Components Standard" • ANSI /TIA/EIA -569 -A and addenda " Commercial Building Standard for Telecommunications Pathways and Spaces" • ANSI /TIA/EIA -606 and addenda "Administration Standard for the Telecommunications Infrastructure of Commercial Buildings" • ANSI /TIA/EIA -607 and addenda " Commercial Building Grounding and Bonding Requirements for Telecommunications" • ANSI /TIA/EIA -526 -7 "Measurement of Optical Power Loss of Installed Single -Mode Fiber Cable Plant" • ANSI /TIA/EIA- 526 -14A "Optical Power Loss Measurements of Installed Mu/timode Fiber Cable Plant" • IEC /TR3 61000 -5 -2 - Ed. 1.0 and amendments "Electromagnetic compatibility (EMC) - Part 5: Installation and mitigation guidelines - Section 2: Earthing and cabling" • ISO /IEC 11801:2000 Edl.2 and amendments " Information technology - Generic cabling for customer premises" • CENELEC EN 50173:2000 and amendments " Information Technology - Generic cabling systems" Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 4 GENERAL REQUIREMENTS Responsive bidders are to provide the following: ■ Insurance Certificate ■ Contractor must have workman's compensation insurance in the state in which work is performed. ■ The Contractor should be prepared to furnish surety, performance and completion bonds if required. ■ Liability ■ Proof of Manufacturers Certification providing City with a minimum 25 years warranty. ■ Proof of RCDD Certificate for staffed employee, if applicable ■ Proof of personnel trained and certified in design and installation of Category 6 cable plant The Structured Cabling System Shall consist of any one or all of the following Elements: ■ Work -Area Cabling • Horizontal Cabling ■ Backbone Fiber Optic & Copper Cabling ■ System shall be capable of supporting Voice, Data, and Video. ■ System shall consist of Unshielded Twisted Pair (UTP) Cable installed in a star topology. It is the Contractors responsibility to maintain cable lengths under the 295 ft. distance limitation. All terminations shall be required to be warranted by Manufacturer, Contractor shall issue a letter of registration prior to start of project to Customer assuring proposed system is in accordance. Contractor shall have a permanent office within 50 miles of the project & be available for after hours emergency service & repair. Contractor must own all equipment, testers & installation tools required for installation of system. Contractor must perform installation with own manpower, no subcontracting of any portion of this RFP will be accepted or allowed. Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 5 SCOPE OF WORK The proposed Cabling System is to be a Category 6 fully compliant & operating system. 5.1 COPPER BACKBONE CABLING Copper backbone cabling shall consist of 100 /50 pair Category 5e riser rated copper cable. Contractor will install a total of (100) pairs of copper cable between MPOE 1 -022 (demark) & the MDF on the 3 d floor, 100 airs of copper cable between MPOE 1 -022 (demark) & the PD Computer room 2 -020 on the 2 nd floor, (100) pairs of copper cable between PD Computer room 2- 020 & the MDF on the 3`d floor, (50) pairs of copper cable between TELCO CLOSET 2 -009 & the MDF on the 3rd floor, (50) pairs of copper cable between TELCO CLOSET 3 -009 & the MDF on the 3`d floor, (50) pairs of copper cable between TELCO CLOSET 4 -009 & the MDF on the 3`d floor, & 50 airs of copper cable between TELCO CLOSET 1 -037 (council chambers) & the MDF on the 3rd floor. The Backbone cables will be terminated onto 300 pair 110 termination blocks. The contractor will then install tails from the blocks onto 96 port Cat 5e Patch panels to facilitate patching of extensions by customer Telecom Personnel. Pair terminations will be 1 pair per port on panels. All necessary wire management shall be installed for a complete system. 5.2 CATEGORY 6 HORIZONTAL CABLING All outlets shall consist of Quad (4) Category 6 Plenum cables installed onto RJ -45 category 6 Outlets. All cable is to be bundled neatly in the ceiling with the use of J- hooks. All cable will be terminated onto 48 port Patch panels in the appropriate IDF. Yellow patch cables shall be provided for port (4) of every location, of sufficient length to connect to data switch at proposed location (as shown in diagrams — see section 14 of the RFP). Orange patch cables shall be provided for port (3) of every location, of sufficient length to connect to data switch at proposed location (as shown in diagrams — see section 14 of this RFP). 5.3 CLOSET TERMINATION All IDF closets will be fitted with (1) 19 "x7' Data Racks. All Horizontal cables will terminate onto 48 port Category 6 patch panels. It is the contractor's responsibility to provide sufficient panels & wire management hardware for a complete system. Racks will be equipped with horizontal & vertical cable management as well as ladder rack for a complete system. All racks to be supplied by contractor Cabinets to be provided by Customer. 5.4 WORK AREA All data outlets shall be supplied with two (2) 10 foot patch category 6 patch cables, one yellow color and one gray color. 5.5 FIBER BACKBONE Fiber backbone cabling shall consist of 12 strands of multimode (62.5/125 um) plus 6 strands of single mode (9/125 um) fiber. Contractor will install fiber backbone between the PD Computer Room 2 -020 and the MDF on the 3`d floor, between the telco closet 2 -009 and the MDF on the 3rd floor, between the telco closet 4 -009 and the MDF on the 3rd floor, and between the telco closet 1 -037 (council chambers) and the MDF on the 3rd floor. In addition, contractor shall supply fiber patch cables for each endpoint as follows: ■ Telco closet 4 -009 : (2) SC -LC 2 meter patch cables • Telco closet 2 -009: (2) SC -LC 2 meter patch cables • Telco closet 1 -037: (2) SC -LC 2 meter patch cables • PD Computer Room : (2) SC -LC 2 meter patch cables • MDF : (8) SC -LC 2 meter patch cables Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 6 BALANCED TWISTED -PAIR PRODUCT SPECIFICATIONS In addition to meeting the proposed category 6 specifications as outlined in ANSI /TIA/EIA- 568 -132 -1, the requirements in this section must also be met for all applicable balanced twisted -pair products as listed below. 6.1 OUTLETS All category 6 information outlets designed for termination of 4 -pair balanced twisted -pair category 6 copper cables must possess the following characteristics at the minimum: 8- position modular jacks (RJ -45) utilizing 568 -B wiring Scheme. Outlet Jack module arrangement & quantities are shown on the drawings. Wall outlets will consist of 6 -port faceplates. Approved Product Leviton or equal. 6.2 PATCH CORDS Approved Product Leviton or equal. 6.3 PATCH PANELS All termination panels shall facilitate cross - connection and inter- connection using modular patch cords and shall conform to EIA standard, 19 inch relay rack mounting requirements. Approved Product Leviton or equal. 6.4 CONNECTING BLOCKS The connecting block shall facilitate cross - connection and /or inter - connection using patch cords /cross connects. Approved Product Leviton or equal. 6.5 CABLE Belden Mediatwist Bonded twisted pair 1874A Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 7 OPTICAL FIBER PRODUCT SPECIFICATIONS In addition to meeting the specifications outlined in ANSI /TIA/EIA- 568 -B.3 and ISO /IEC 11801:2000 Edl .2, the requirements in this section must also be met for all applicable optical fiber products as listed below. 7.1 OUTLETS /ADAPTERS All optical fiber outlets /adapters shall meet the following characteristics: Approved Product Leviton or equal. 7.2 CONNECTORS All optical fiber connectors shall meet the following characteristics: Approved Product Leviton or equal. 7.3 PATCH CORDS /PIGTAILS Fiber equipment cords shall possess the following characteristics: Approved Product Leviton or equal. 7.4 ENCLOSURES All interconnect centers, panels and trays (units) shall provide cross - connect, inter - connect, splicing capabilities and contain cable management for supporting and routing the fiber cables /jumpers. Approved Product Leviton or equal. 7.5 CABLE In addition to meeting the applicable performance specifications, all optical fiber cable shall be appropriate for the environment in which it is installed. All backbone fiber optic cable shall be 12 strand Multimode riser rated cable, 62.5/125um & 6 strand 9/125um Single mode. Fiber optic cable shall be Riser (OFNR) or Plenum (OFNP) listed where available. Each fiber outlet will be terminated onto SC connectors at both ends for multimode fiber & FC connectors at both ends for single mode fiber. Fiber pair terminations are to be reversed (swapped) on IDF side. Approved product CORNING 12 strand riser rated 62.51125um fiber optic Multimode cable CORNING 6 strand riser rated 91125um fiber optic Single Mode cable Contractor will install a total of (12 MM / 6 SM) Fiber Optic cable Strands between the PD Computer room 2 -020 & the MDF on the 3 rd floor, (12 MM / 6 SM) Fiber Optic cable Strands between TELCO CLOSET 2 -009 & the MDF on the 3rd floor, (12 MM / 6 SM) Fiber Optic cable Strands between TELCO CLOSET 4 -009 & the MDF on the Y floor, & (12 MM / 6 SM) Fiber Optic cable Strands between TELCO CLOSET 1 -037 (council chambers) & the MDF on the 3` floor. Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 8 MOUNTING OPTIONS 8.1 FACEPLATES Approved Product Leviton or equal. 8.2 RACKS For rack mounted installations in a telecommunications room the installer shall use a 19 inch equipment rack. CHATSWORTH Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 9 SYSTEM DESIGN REQUIREMENTS 9.1 HORIZONTAL CABLING The Horizontal Subsystem is the portion of the telecommunications cabling system that extends from the work area telecommunications outlet/connector to the horizontal cross - connect in the telecommunications room. It consists of the telecommunications outlet/connector, the horizontal cables, optional consolidation point, and that portion of the cross - connect in the telecommunications room serving the horizontal cable. 9.2 BACKBONE CABLING 9.2.1 INTRABUILDING CABLING All cable will be installed via a conduit system that will be in place prior to start of project. This system will be used to connect the main equipment/computer (MDF) room to the (IDF) closets. Data Backbone will consist of Multimode Fiber optic cabling, 12- strand 62.5/125um & 6- strand 9/125um Single Mode fiber optic, manufactured by Commscope or approved equal. Voice riser shall consist of 100 or 50 pair category 5e. 9.2.2 INTERBUILDING CABLING When a distribution system encompasses more than one building, the components that provide the link between buildings constitute the Interbuilding Backbone Subsystem. This subsystem includes the backbone transmission media, associated connecting hardware terminating this media, and electrical protection devices to mitigate harmful voltages when the media is exposed to lightning and /or high voltage power surges that pass through the building cable. It is normally a first -level backbone cable beginning at the main cross - connect in the equipment room of the hub building and extending to the intermediate cross - connect in the equipment room of a satellite building. Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 10 INSTALLATION 10.1 SITE SURVEY Prior to placing any cable pathways or cable, the contractor shall survey the site to determine job conditions will not impose any obstructions that would interfere with the safe and satisfactory placement of the cables. The arrangements to remove any obstructions with the Project Manager need to be determined at that time. 10.2 PHYSICAL INSTALLATION 10.2.1 CABLE PATHWAYS ■ Pathways shall be designed and installed to meet applicable local and national building and electrical codes or regulations. • Grounding / Earthing and bonding of pathways shall comply with applicable codes and regulations. • Pathways shall not have exposed sharp edges that may come into contact with telecommunications cables. • The number of cables placed in a pathway shall not exceed manufacture specifications, nor, will the geometric shape of a cable be affected. • Pathways shall not be located in elevator shafts. 10.2.2 INTRABUILDING CABLE ROUTING ■ The backbone subsystem shall include cable installed in a vertical manner between floor telecommunications rooms and the main or intermediate cross - connect in a multi -story building and cable installed horizontally between telecommunications rooms and the main or intermediate cross - connect in a long single story building like a school or factory. ■ Unless otherwise recommended by the manufacturer, all fiber cables will be run in inner duct. ■ Fibers will be terminated in the telecommunications rooms using SC, or FC connectors in wall mounted interconnect centers or rack mounted panels equipped with sufficient ports, slack storage space and splice trays if required to terminate and secure all fibers. • Adequate riser sleeve /slot space shall be available with the ability to ingress the area at a later date in all telecommunications rooms, such that no drilling of additional sleeves /slots is necessary. • The backbone cables shall be installed in a star topology, emanating from the main cross - connect to each telecommunications room. An intermediate cross - connect may be present between the main cross - connect and the horizontal cross - connect. This is known as a hierarchical star topology. • Optical fiber should be run for any backbone segment greater than 90 m (295 ft.). If the Intrabuilding backbone segment is less than 90 m (295 ft), and fiber is not routed, the balanced twisted -pair cable shall be category 5e or higher. • Backbone pathways shall be installed or selected such that the minimum bend radius of backbone cables is kept within manufacturer specifications both during and after installation. • In an underground system, adequate underground conduit space shall be available and accessible at each building. The conduits shall not exceed a fill factor of 40 %. ■ All underground systems shall be designed to prevent water runoff from entering the building. ■ The backbone cables shall be installed in a star topology, emanating from the main cross - connect to each satellite building telecommunications room. All Interbuilding cables shall be installed to the applicable codes and regulations. 10.2.3 HORIZONTAL CABLE ROUTING ■ All horizontal cables, regardless of media type, shall not exceed 90 m (295 ft) from the telecommunications outlets in the work area to the horizontal cross connect. Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary • The combined length of jumpers, or patch cords and equipment cables in the telecommunications room and the work area should not exceed 10m (33 ft) unless used in conjunction with a multi -user telecommunications outlet. • Two horizontal cables shall be routed to each work area. At least one horizontal cable connected to an information outlet shall be 4 -pair, 100 Q balanced twisted -pair. • It is recommended that a minimum horizontal cable distance of 15m (49 ft.) shall be maintained between the telecommunications room and the work area. • Horizontal pathways shall be installed or selected such that the minimum bend radius of horizontal cables is kept within manufacturer specifications both during and after installation. • In open ceiling cabling, cable supports shall be provided by means that is structurally independent of the suspended ceiling, its framework, or supports. These supports shall be spaced no more than 1.5 m (5 ft) apart. • Telecommunications pathways, spaces and metallic cables, which run parallel with electric power or lighting, which is less than or equal to 480 Vrms, shall be installed with a minimum clearance of 50 mm (2 in). • The installation of telecommunications cabling shall maintain a minimum clearance of 3 m (10 ft) from power cables in excess of 480 Vrms. • No telecommunications cross - connects shall be physically located within 6 m (20 ft) of electrical distribution panels, step down devices, or transformers, which carry voltages in excess of 480 Vrms. • For voice or data applications, 4 -pair balanced twisted -pair or fiber optic cables shall be run using a star topology from the telecommunications room serving that floor to every individual information outlet. The customer prior to installation of the cabling shall approve all cable routes. • The Contractor shall observe the bending radius and pulling strength requirements of the 4 -pair balanced twisted -pair and fiber optic cable during handling and installation. • Each run of balanced twisted -pair cable between horizontal portions of the cross - connect in the telecommunication closet and the information outlet shall not contain splices. • In a false ceiling environment, a minimum of 3 inches (75 mm) shall be observed between the cable supports and the false ceiling. • Continuous conduit runs installed by the contractor should not exceed 30.5 m (100 ft) or contain more than two (2) 90 degree bends without utilizing appropriately sized pull boxes. • All horizontal pathways shall be designed, installed and grounded to meet applicable local and national building and electrical codes. • Maximum conduit pathway capacity shall not exceed a 40% fill. However, perimeter and furniture fill is limited to 60% fill for move and changes. • Horizontal distribution cables shall not be exposed in the work area or other locations with public access. • Cables routed in a suspended ceiling shall not be draped across the ceiling tiles. Cable supports shall be mounted a minimum of 75 mm (3 in) above the ceiling grid supporting the tiles. 10.2.4 WORK AREA TERMINATION ■ All balanced twisted -pair cables wired to the telecommunications outlet/connector, shall have 4 -pairs terminated in eight - position modular outlets in the work area. All pairs shall be terminated using a EIA/TIA 568 -b Wiring Scheme. ■ The telecommunications outlet/connector shall be securely mounted at planned locations. ■ The height of the telecommunications faceplates shall be to applicable codes and regulations. 10.2.5 PULLING TENSION ■ The maximum cable pulling tensions shall not exceed manufacturer's specifications. Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 10.2.6 BEND RADIUS ■ The maximum cable bend radii shall not exceed manufacturer's specifications. ■ In spaces with balanced twisted -pair cable terminations, the maximum bend radius for 4 -pair cable shall not exceed four times the outside diameter of the cable and ten times for multi -pair cable. This shall be done unless this violates manufacturer specifications. ■ During the actual installation, bend radius on 4 -pair cable shall not exceed eight times the outside diameter of the cable and ten times for multi -pair cable. This shall be done unless this violates manufacturer specifications. 10.2.7 SLACK ■ In the work area, a minimum of 300 mm (12 in) should be left for balanced twisted -pair cables, while 1 m (3 ft) is left for fiber cables. ■ In telecommunications rooms a minimum of 3m (10 ft) of slack should be left for all cable types. This slack must be neatly managed on trays or other support types. 10.2.8 CABLE TIE WRAPS ■ Tie wraps shall be used at appropriate intervals to secure cable and to provide strain relief at termination points. These wraps shall not be over tightened to the point of deforming or crimping the cable sheath. ■ Hook and loop cable managers should be used in the closet where reconfiguration of cables and terminations may be frequent. 10.2.9 GROUNDING ■ All grounding / earthing and bonding shall be done to applicable codes and regulations. 10.2.10 FIRE PROTECTION ■ Properly installed fire stop systems shall be installed to prevent or retard the spread of fire, smoke, water, and gases through the building. This requirement applies to openings designed for telecommunications use that may or may not be penetrated by cables, wires, or raceways. ■ Fire stops shall be done to applicable code. 10.2.11 WORKMANSHIP • All work shall be done in a workman like fashion of the highest standards in the telecommunications industry. • All equipment and materials are to be installed in a neat and secure manner, while cables are to be properly dressed. • Workers must clean any debris and trash at the close of each workday. Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 11 TESTING Testing of all newly installed cable channels shall be performed prior to system cutover. 11.1 COPPER TESTING ■ All category 6 field testing shall be performed with an approved level III balanced twisted -pair field test device. ■ All installed category 6 channels shall perform equal to or better than the minimum requirements as specified by the table below: Parameter 100MHz (dB) 200MHz (d B) 250MHz dB) 300MHz (dB) Insertion Loss 19.0 dB 27.4 dB 30.9 dB 34.1 dB NEXT Loss 43.9 dB 39.3 dB 37.8 dB 36.6 dB PS NEXT Loss 41.9 dB 37.3 dB 35.8 dB 34.6 dB ACR 24.9 dB 11.9 dB 6.9 dB 2.5 dB PS ACR 22.9 dB 9.9 dB 4.9 dB 0.5 dB ELFEXT 26.3 dB 20.3 dB 18.3 dB 16.8 dB PS ELFEXT 23.4 dB 17.3 dB 15.4 dB 13.8 dB Return Loss 14.7 dB 11.7 dB 10.7 dB 9.9 dB Propagation Delay 528 ns 527 ns 526 ns 526 ns Delay Skew 40 ns 40 ns 40 ns 40 ns ■ Category 6 balanced twisted -pair horizontal and backbone cables, whose length does not exceed 90 m (295 ft) for the basic link, and 100 m (328 ft) for the channel shall be 100 percent tested according to ANSI /TIA/EIA- 568 -B.1. Test parameters include wire map plus ScTP shield continuity (when present), length, NEXT loss (pair -to- pair), NEXT loss (power sum), ELFEXT loss (pair -to- pair), ELFEXT loss (power sum), return loss, insertion loss, propagation delay, and delay skew. TEST EQUIPMENT CRITERIA • All balanced twisted -pair field testers shall be factory calibrated each calendar year by the field test equipment manufacturer as stipulated by the manuals provided with the field test unit. The calibration certificate shall be provided for review prior to the start of testing. • Auto test settings provided in the field tester for testing the installed cabling shall be set to the default parameters • Test settings selected from options provided in the field testers shall be compatible with the installed cable under test. 11.2 FIBER OPTIC TESTING HORIZONTAL FIBER TESTING ■ Fiber horizontal cables shall be 100% tested for insertion loss and length. • Insertion loss shall be tested at 850 nm or 1300 nm for 50/125µm and 62.5/125µm multimode cabling in at least one direction using the Method B (1- jumper) test procedure as specified in ANSI /TIA/EIA- 526 -14A. • Length shall be tested using an OTDR, optical length test measurement device or sequential cable measurement markings. BACKBONE FIBER TESTING • Fiber horizontal cables shall be 100% tested for insertion loss and length. ■ Insertion loss shall be tested at 850 nm and 1300 nm for 50/125µm and 62.5/125µm multimode cabling in at least one direction using the Method B (1- jumper) test procedure as specified in ANSI /TIA/EIA- 526 -14A. Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary • Insertion loss shall be tested at 1310 and 1550 for single mode cabling in at least one direction using the Method A.1 (1- jumper) test procedure as specified in ANSI /TIA/EIA- 526 -7. • Length shall be tested using an OTDR, optical length test measurement device or sequential cable measurement markings. Category 6 Cabling System City of Sunny Isles Beach Request for Proposal Confidential and Proprietary 12 ADMINISTRATION & DOCUMENTATION 12.1 LABELING ■ Horizontal and backbone cables shall be labeled at each end. The cable or its label shall be marked with its identifier. ■ A unique identifier shall be marked on each faceplate to identify it as connecting hardware. ■ Each port in the faceplate shall be labeled with its identifier. ■ A unique identifier shall be marked on each piece of connecting hardware to identify it as connecting hardware. ■ Each port on the connecting hardware shall be labeled with its identifier. 12.2 DRAWINGS As -built drawings shall be supplied by the contractor showing the locations of and identifiers for all: ■ Horizontal cable routing and terminations ■ Telecommunications outlets /connectors ■ Backbone cable routing and terminations 12.3 RECORDS All records shall be created by the installation contractor and turned over at the completion of work The format shall be computer based and both soft copies and hard copies shall be part of the As -built package. The minimum requirements include: • Cable records must contain the identifier, cable type, termination positions at both ends, splice information as well as any damaged pairs /conductors. • Connecting hardware and connecting hardware position records must contain the identifier, type, damaged position numbers, and references to the cable identifier attached to it. • Test documentation on all cable types shall be included as part of the As -built package. 12.4 REPORTS All reports shall be generated from the computer based program used to create the records above. These reports should include but not limited to; ■ Cable Reports ■ Cross - connect Reports ■ Connecting Hardware Reports fiEINVI V :", kgkw/ Either a basic link or channel model configuration may be applied to the horizontal and /or backbone sub - systems of the structured cabling system. Applications assurance is only applied to a channel model configuration. All channels are to be qualified for linear transmission performance up to 300 MHz to ensure that high- frequency voltage phase and magnitude contributions do not prove cumulative or adversely affect channel performance. 13.1 SYSTEM WARRANTY A twenty (25) year warranty available for pending category 6 structured cabling system shall be provided for an end -to -end channel model installation which covers applications assurance, cable, connecting hardware and the labor cost for the repair or replacement thereof. Additional features of the warranty shall include: ■ Margin over proposed category 6 channel specifications on all parameters across the entire frequency range of 1- 300MHz as noted below: Parameter Guaranteed Margin 1 -300 MHz (dB) Insertion Loss 0.1 dB NEXT Loss 2.9 dB PS NEXT Loss 3.5 dB ACR 3.1 dB PS ACR 3.6 dB ELFEXT 3.0 dB PS ELFEXT 3.0 dB Return Loss 0.6 dB Propagation Delay 20 ns Delay Skew 10 ns ■ Performance claims based on worst case testing and channel configurations ■ Applications will not exceed bit error rates specified by IEEE, ATM Forum, ANSI and ISO standards for all current and future applications operating on compliant LAN equipment that has been designed for use with a compatible category or class of balanced twisted -pair cabling. 13.2 PRODUCT WARRANTY The manufacturer of passive telecommunications equipment used in a manner not associated with the Systems Warranty must have a minimum five (5) year Component Warranty on all its product. The Products Warranty covers the components against defects in material or workmanship under normal and proper use. 13.3 APPLICATIONS SUPPORTED Existing and future applications supported for a channel model warranty include those approved by the Institute of Electronic and Electrical Engineers (IEEE), the Asynchronous Transfer Mode (ATM) Forum, the American National Standards Institute (ANSI) or the International Organization of Standards (ISO) that specify compatibility with the cable referenced herein. 14 ATTACHMENTS 14.1 VERTICAL RISER DIAGRAM New City Hall Vertical Cabling Telco Closet 0 .... 0-1 4 -009 ----------------- - - - - -- ---- - - - - -- ------ - - - - -- Telco Closet 3 -009 i O ------------------ - - - - -- Telco Closet 2 -009 Computer Room 3 -016 _ PD Computer Room MPOE 1 -022 (demarc) 1 Telco Closet 1 -037 (council chambers) r=1 / • Page 1 (/ j 2 multi mode + 6 single mode fiber = 100 pair Cat5e feeder Cr = 50 pair Cat5e feeder 4th Floor 3rd Floor 2nd Floor 1 st Floor 14.2 HORIZONTAL RISER DIAGRAM New City Hall Horizontal Cabling Telco Closet _ _ _ _ _ _ _ _ — — — 0 Floor Datalloice 4 -009 1 38 locations Telco Closet 3 -009 4th Floor I I I Telco Closet PD Computer _ _ _ _ _ _ _ _ 2^° Floor Datalloice 2nd 2 -009 Room - 34 locations Floor I I I I I I I - - — — — — 2Cat6 I I -- -a------- -- - - - - -I I I 3rd Computer -- 3' Floor Datalloice — — - (3 ---- . Floor Room 3 -016 Non -PD area 40 locations MPOE 1 -022 l i 3r° Floor Datalloice — PD area 12 locations I I I Telco Closet PD Computer _ _ _ _ _ _ _ _ 2^° Floor Datalloice 2nd 2 -009 Room - 34 locations Floor I I I I I I I - - — — — — 2Cat6 I I -- -a------- -- - - - - -I I I II II �I MPOE 1 -022 l i Telco Closet 1 -037 (demarc) (council chambers) 1St I I Floor I 1" Floor Datalloice I t I Public Works 6locations ! Post Office 3locations ly_ 1" Floor Datalloice t — ,Council Chambers Library 15 locations Conf Room 8locations Datalloice 15 locations Main 6 locations /= Page 1 4 Cat6 cables (unless otherwise noted) „, 14.3 1 ST FLOOR TELCO CLOSET LAYOUT Project i — li qiI . ..egeM SIB City Hall - Telco Closet 1" Floor (Council Chambers) J, Revisetl Drawn By Page Room Layout Derrick L Arias 1 of 2 14.4 1" FLOOR TELCO CLOSET RACK DESIGN 42U Rack 8 8 8 8 42 P40 8 SI CABLE MANAGEMEM 8 39 8 38 8 8 .Q 8 8 8 CABLE MANAGEMEN- 8 37 8 36 8 35 8 34 8 33 8 32 8 8 CABLE MANAGEMEN- 8 31 8 30 8 8 8 29 8 28 .Q 8 CABLE MANAGEMEN- 8 27 8 26 8 8 SI 8 CABLE MANAGEMEN- ... .........� 8 25 8 24 8 23 8 22 8 21 81, _ [ ir.r..� ...._ g 20 8 8 8 8 8 8 8 8 8 8 8 8 8 8 19 8 18 8 17 8 16 8 15 8 14 8 13 8 12 8 11 8 10 8 9 8 8 8 7 z - 6 5 4 3 2 1 Fiber Panel to Main computer room on 3rd 1� floor cables (chambers) — Locations 1 -16 White cables 1" floor cables (chambers) —Locations 1 -16 Black cables 1� floor cables (chambers) — Locations 1 -16 Orange cables 1�' floor cables (chambers) — Locations 1 -16 Yellow cables Procurve 2824 Procurve 2824 SU2200RMXL3U SU48R3XLBP J r U ca m 3 � o` O U N N m O d N to ;_ r U U C N 0 U ma J O U .- N � N s o CL 0 U C) x o N O N N U C6 m m � a cn Q I 14.52 ND FLOOR TELCO CLOSET LAYOUT _ - Project Dewing Title Legend L- SIB City Hall - Telco Closet 2 "' Floor Revised D2wnRy Pa P Room Layout Apr 8. 2004 Derrick L Arias 1 0l 2 14.62 ND FLOOR TELCO CLOSET RACK DESIGN 42U Rac7k-7] 8 8 42 8 8 8 41 8 40 SI 8 CABLE MANAGEMEN- 8 39 8 38 8 8 .Q 8 8 8 CABLE MANAGEMEN- 8 37 8 36 8 35 8 34 8 33 8 32 8 o 8 CABLE MANAGEMEN- 8 31 8 30 8 8 18 18 29 28 .Q 8 CABLE MANAGEMEN- 8 27 8 26 8 8 8I 8 8 VO CABLE MANAGEMEN- .......... 8 25 8 24 8 23 8 22 8 21 8 8 8 8 8 8 8 8 8 8 8 81 8 19 8 18 8 17 8 16 8 15 8 14 8 13 8 12 8 11 8 10 8 9 8 8 8 7 6 5 4 3 Fiber Panel to Main computer room on 3rd 1" Floor cables —Locations 1 -38 White cables 1" floor cables — Locations 1 -38 Black cables �1" — Locations 1 -38 ge cables 1" floor cables —Locations 1 -38 Yellow cables Procurve 2824 Procurve 2824 SU2200RMXL3U SU48R3XLBP J r U m � 3 CV o p U N N L O d N a 0 (L N N co Q y 3J O m U m o O U Q a _a CU Co C) 0 �o y N N � a Q 14.74 TH FLOOR TELCO CLOSET LAYOUT Project Drawing Title Legend SIB City Hall - Telco Closet 4" Floor .�' Rehsed Drawn B9, Room Layout Apr 8, 2004 Derrick L. Arias 1 of 2 14.84 TH FLOOR TELCO CLOSET RACK DESIGN 42U Rack 8 8 8 8 42 8 41 8 40 Si 8 CABLE MANAGEMEN- 8 39 8 38 8 8 11 CABLE MANAGEMEN- 8 8 8 181 8 37 8 36 8 35 8 34 8 33 32 8 CABLE MANAGEMEN- 8 8 31 8 30 8 8 8 29 8 28 SI CABLE MANAGEMEN- 8 8 27 8 26 8 8 S ) CABLE MANAGEMEN- 8 e> 222k �:���� 8 25 8 24 8 23 8 22 8 21 8 - , 8 20 8 8 8 8 8 8 8 8 8 8 8 8 8 8 19 8 18 8 17 8 16 8 15 8 14 8 13 8 12 8 11 8 10 8 9 8 8 8 7 ate.. 6 5 4 _ °W` 3 2 1 Fiber Panel to Main computer room on 3rd 4`" floor cables — Locations 1-40 White cables 4" floor cables — Locations 1 -40 Black cables 4`" floor cables — Locations 1 -40 Orange cables 4' "floor cables — Locations 1 -40 Yellow cables Procurve 2824 Procurve 2824 SU2200RMXL3U SU48R3XLBP 14.92 ND FLOOR COMPUTER ROOM LAYOUT LN- 5'B Gty "a" PD Computer // Revised Drawn By Page Apr 8, 2004 Demck L. Arias 1 of 4 Rnnm 14.102 ND FLOOR COMPUTER ROOM RACK 1 DESIGN 42U Rack 8 42 8 41 1 CABLE MANAGEMEW 8 39 CABLE MANAGEMEW CABLE MANAGEMEW CABLE MANAGEMEW CABLE MANAGEMEW CABLE MANAGEMEW CABLE MANAGEMEW 111 36 181351 32 31 28 27 24 18123 21 20 19 Aml Ice 0 0 f 3re Floor Cables — Locations 1 -10 (White) 3rd Floor Cables — Locations 1 -10 (Black) 3rd Floor Cables —Locations 1 -10 (Orange) 3rd Floor Cables — Locations 1 -10 (Yellow) I 1" Floor Cables — Locations 1 -8 (White) I 1" Floor Cables — Locations 1 -8 (Black)1 1" Floor Cables — Locations 1 -8 (Orange) 1" Floor Cables — Locations 1 -8 (Yellow 3rd Floor Cat5e 100 -pair Feeder —Locations 1 -24 (To Main Computer Room) 1" Floor Cat5e 100 -pair Feeder — Locations 1 -24 (To MPOE) County Connection NCIC /FCIC d J r m L.L o Q aN N (0 co C J (0 U_ S O" o � � a m U) v �o N N 06 .� 0-t- � a Q 14.11 2 "D FLOOR COMPUTER ROOM RACK 2 DESIGN 42U Rack 8 8 42 8 8i 8 8 8 8i 8 8 8 CABLE MANAGEMEN- CABLE MANAGEMEN- 8 40 8 39 8 43&1 8 37 8 36 8 35 8 434— 8 33 8 8 CABLE MANAGEMEN- 8 32 8 31 8 8 8 29 8I CABLE MANAGEMEN- 8 28 8 8 8 25 8I CABLE MANAGEMEN- g 23 8 8 8 Fiber Patch Panel 8 22 8 20 8 - ....._..* a.. *.. *... ®ei 8 19 8 : U91 ®.: ..... *' �... ®��......s. �... �. 17 8 16 15 8 8 8 8 8 8 8 8 8 8 8 8 8 14 8 13 8 12 8 11 8 10 8 9 8 8 8 7 8 6 8 5 8 4 8 3 8 2 8 1 Cross - Connect to Cabinetl 2 "d Floor Cables — Locations 1 -36 White cables 2nd Floor Cables — Locations 1 -36 Black cables 2 "d Floor Cables — Locations 1 -36 Orange cables 2nd Floor Cables — Locations 1 -36 Yellow cables Fiber to 3rd Floor Main computer Room Procurve 4108GL 14.12 2 "D FLOOR COMPUTER ROOM CABINET 1 DESIGN c m J ^ -0 W N O1 3 U 0 a. m� �o a� N N m Q C U = m v 0 Do � N N > C6 2 a Q 14.133 RD FLOOR COMPUTER ROOM LAYOUT o 2,_0. N N O N Copper backbone cabling terminates in this closet / Project Draw,q idle Legentl I SIB City Hall -Main Computer Room 3'0 Floor -% Revisetl Dravm By Page Room Layout Apr 8, 2064 Derrick L. Arias i of 7 14.143 RD FLOOR COMPUTER ROOM RACK 1 DESIGN 42U Rack - 8 8 42 8 8 41 giCABLE MANAGEMEN- 8 39 CABLE MANAGEMEN" CABLE MANAGEMEN" CABLE MANAGEMEN- CABLE MANAGEMEW CABLE MANAGEMEN- CABLE MANAGEMEN" 1 a 37 8 36 8 35 8 34 32 31 30 29 27 26 25 24 22 21 20 19 17 16 15 13 12 11 10 9 8 7 6 5 4 3 2 1 PD Computer Room fiber patch panel 4`h floor fiber patch panel 2 "d floor fiber patch panel 1 s' floor fiber patch panel 2nd Floor Cat5e 100 -pair feeder —Locations 1 -24 (To PD Computer Room) 1" Floor Cat5e 100 -pair feeder — Locations 1 -24 (To MPOE) Ell� Project Drawing iifle Legend SIB City Hall - Main Computer Room 3' Floor Re lsed orawney Page Rackl Apr 8, 2004 Derrick L. Arias 2 of 7 14.153 RD FLOOR COMPUTER ROOM RACK 2 DESIGN 42U Rack 8 8 -0 8 8 S I 8 CABLE MANAGEMEN- 18 CABLE MANAGEMEN- 8 41 8 9 37 8 36 8 35 8 8 8 33 Si 8 CABLE MANAGEMEN- 8 32 8 31 8 a 8 Q- 8 29 8 8 CABLE MANAGEMEN" 9 28 8 27 8 8 8 .0 CABLE MANAGEMEN" 8 8 25 24 8 23 8 8 SI 8 18 CABLE MANAGEMEN" 21 8 20 8 19 8 8 .Q 8 CABLE MANAGEMEN 8 16 8 15 8.,: .o__ __ 8 14 g ...... ®....:, ®. .....� .... �,...,.. �.s ® 8 13 12 8 8 11 8 ,-. 8 10 8 8 8 8 9 8 8 8 7 Aj?c 6 5 4 _ 3 2 1 3rd floor cables — Locations 1 -42 White cables 3rd floor cables — Locations 1 -42 Black cables 7:1 3rtl floor cables — Locations 1 -42 Orange cables 3rd floor cables — Locations 1 -42 Yellow cables 48 -port cross connect to Cabinet f 48 -port cross connect to Cabinet 2 71 24 -port cross connect to Rack 3 24 -port cross connect to Rack 4 Procurve 4108GL SU2200RMXL3U SU48R3XLBP Project Drawing Title Legend j SIB City Hall - Main Computer Room 3° Floor �[ J� Revised Drawn By Page Rack2 Apr 8, 2004 Derrick L. Arias 3 of 7 14.163 RD FLOOR COMPUTER ROOM RACK 3 DESIGN 42U Rack 8 8 42 8 8I CABLE MANAGEMEW 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 9 8 38 8 37 8 36 8 35 8 34 8 33 8 32 8 31 8 30 8 29 8 28 8 27 8 26 8 25 24 8 23 8 22 8 21 8 20 8 19 8 18 8 17 8 16 8 15 8 14 8 13 8 12 8 11 8 10 8 9 8 8 8 7 8 6 8 5 8 4 8 3 8 2 8 1 24 -port cro,s connect to Rack 2 Project Drawing Ttle Legend SIB City Hall - Main Computer Room 3" Floor Revised 04 Page RaW Apr B, 2004 Derrick L. Arias 4 0 77 14.173 RD FLOOR COMPUTER ROOM RACK 4 DESIGN 42U Rack 24 -port cross - connect to Rack 2 Project Drawing Title Legend I� SIB City Hall - Main Computer Room 3" Floor \) Revised Drawn By Page Rack4 Apr 8, 2004 Derrick L. Arias 5 of 7 8 8 8 8 8 8 8 8 8 8 8 Shelf for AS /400 mini (14U) 8 41 8 40 8 39 8 38 8 37 8 36 8 35 8 34 8 33 8 32 8 31 8 30 29 28 8 8 8 8 8 8 8 8 8 8 27 8 26 81 25 81 24 8 23 8 22 8 21 8 20 8 19 10U Rack Mount Monitor (17) 8 18 8 8 8 8 8 8 8 8 8 8 Shelf for AS1400 mini (14U) 8 17 8 16 8 15 8 14 8 13 8 12 11 10 8 9 8 8 8 7 8 6 8 5 4 AS /400 UPS (Existing) 3 2 8 18 1 24 -port cross - connect to Rack 2 Project Drawing Title Legend I� SIB City Hall - Main Computer Room 3" Floor \) Revised Drawn By Page Rack4 Apr 8, 2004 Derrick L. Arias 5 of 7 14.183 RD FLOOR COMPUTER ROOM CABINET 1 DESIGN \ Project Drawing Title Legend SIB City Hall - Main Computer Room 3" Floor �) Revised Drawn By Page Cabinet 1 - Apr 8, 2004 Derrick L. Arias r: nn 7 14.193 RD FLOOR COMPUTER ROOM CABINET 2 DESIGN Project Drawing Title Legend I SIB City Hall - Main Computer Room 3r° Floor /'+ Revised Drawn By Page Cabinet 2 Apra, 2004 Dernck L. Arias 7 of 7 14.20 ARCHITECTURAL DRAWINGS Respondees should reference building plans for outlet locations. The sheets containing architectural drawings may be obtained from: ■ Miami T- Square ■ Project Name: Sunny Isles Government Center ■ All Electrical Sheets Revision 21 ■ Dated March 26, 2004 15 INSURANCE REQUIREMENT The Successful contractor shall purchase & maintain for protection from claims under worker's compensation acts, claims resulting from negligent acts for damages of bodily injury, claims for damages because of injury to or destruction of personal property including loss of use resulting there from & claims arising out of the performance of this agreement. All insurance provided under this contract shall be through an insurance carrier acceptable to the customer. ■ Worker's Compensation Statutory ■ Liability Combined limit ■ Bodily injury: each person $1,000,000.00 • Bodily Injury: Each accident $1,000,000.00 • Property Damage: Each accident $1,000,000.00 ■ Automobile Liability & Property Damage Combined Limit ■ Bodily injury: each Person $200,000.00 ■ Bodily injury $500,000.00 ■ Property Damage $100,000.00 Prior to start of any work under this contract, the successful contractor shall provide to the City the above referenced insurance certificate. Contractor shall notify City in writing (30) days prior to any changes, cancellation or revocation of above coverage's. It is the contractor's responsibility to maintain the above referenced insurance for the duration of the project. Failure to provide such coverage's shall deem contractor non - responsive & null any & all contracts. SWORN STATEMENT PURSUANT TO SECTION 287.133(3)(a) FLORIDA STATUTES, ON PUBLIC ENTITY CRIMES THIS FORM MUST BE SIGNED AND SWORN TO IN THE PRESENCE OF A NOTARY PUBLIC OR OTHER OFFICIAL AUTHORIZED TO ADMINISTER OATHS. 1 . This sworn statement is submitted to by for whose business address is and (if applicable) its Federal Employer Identification Number (FEIN) is OF the entity had no FEIN, include the Social Security Number of the individual signing this sworn statement: 2. 1 understand that a "public entity crime" as defined in Paragraph 287.133(1)(g), Florida Statutes, means a violation of any state or federal law by a person with respect to and directly related to the transaction of business with any public entity or with an agency or political subdivision of any other state or of the United States, including, but not limited to, any bid or contract for goods or services to be provided to any public entity or an agency or political subdivision of any other state or of the United States and involving antitrust, fraud, theft, bribery, collusion, racketeering, conspiracy, or material misrepresentation. 3. 1 understand that "convicted" or "conviction" as defined in Paragraph 287.133(I)(b), Florida Statutes means a finding of guilt or a conviction of a public entity crime, with or without an adjudication of guilt, in any federal or state trial court of record relating to charges brought by indictment or information after July 1, 1989, as a result of a jury verdict, nonjury trial, or entry of a plea of guilty or nolo contenders. 4. I understand that an "affiliate" as defined in Paragraph 287.1330)(a), Florida Statutes, means: a. A predecessor or successor of a person convicted of a public entity crime; or b. An entity under the control of any natural person who is active in the management of the entity and who has been convicted of a public entity come. The term "affiliate" includes those officers, directors, executives, partners, shareholders, employees, members, and agents who are active in the management of an affiliate. The ownership by one person of shares constituting a controlling interest in another person, or a pooling of equipment or income among persons when not for fair market value under an arm's length agreement, shall be a prima facie case that one person controls another person. A person who knowingly enters into a joint venture with a person who has been convicted of a public entity crime in Florida during the preceding 36 months shall be considered an affiliate. I understand that a "person" as defined in Paragraph 287.133(I)(e), Florida Statutes, means any natural person or entity organized under the laws of any state or of the United States with the legal power to enter into a binding contract and which bids or applies to bid on contracts for the provision of goods or services let by a public entity, or which otherwise transacts or applies to transact business with a public entity. The term "person" includes those officers, directors, executives, partners, shareholders, employees, members, and agents who are active in management of any entity. Signature Date Sworn to and subscribed before me this day of , 2004, by who is personally known to me or has provided as identification. Notary Seal: Notary Signature NON - COLLUSIVE AFFIDAVIT State of )ss County of ) being first duly sworn, deposes and says that: (1) He /she is the Owner, Partner, Officer, Representative or Agent of the Bidder that has submitted the attached Bid; (2) He /she is fully informed respecting the preparation and contents of the attached Bid and of all pertinent circumstances respecting such Bid; (3) Such Bid is genuine and is not a collusive or sham Bid; (4) Neither the said bidder nor any of its officers, partners, owners, agents, representatives, employees or parties in interest, including this affiant, have in any way colluded, conspired, connived or agreed, directly or indirectly, with any other Bidder, firm, or person to submit a collusive or sham Bid in connection with the Work for which the attached Bid has been submitted; or to refrain from bidding in connection with such Work, or have in any manner, directly or indirectly, sought by agreement or collusion, or communication, or conference with any Bidder, firm, or person to fix the price or prices in the attached Bid or of any other Bidder, or to fix any overhead, profit, or cost elements of the Bid price or the Bid price of any other Bidder, or to secure through any collusion, conspiracy, connivance, or unlawful agreement any advantage against the City of Sunny Isles Beach, or any person interested in the proposed Work; (5) The price or prices quoted in the attached Bid are fair and proper and are not tainted by any collusion, conspiracy, connivance, or unlawful agreement on the part of the Bidder or any other of its agents, representatives, owners, employees or parties in interest, including this affiant. Sworn to and subscribed before me this day of , 2004, by who is personally known to me or has provided as identification. Notary Seal: Notary Signature t Request For Proposal #04 -04 -01 For a Category 6 Structured Cabling System At Sunny Isles Government Center Sunny Isles Beach, FL 1 Addendum 1 This addendum is issued to clarify and correct information in the original bid package, as a result of the pre -bid conference held Monday, April 26. Must the system be designed to meet manufacturer's warranty requirements? If so, can the appropriate manufacturer components be substituted for those specified in the RFP? ➢ Yes, the system must be designed to meet manufacturer warranty requirements, and appropriate manufacturer components may be substituted for those specified in the RFP in order to meet the manufacturer warranty requirements. 2. The RFP specifies 50 or 100 pair Cat5e to be installed as part of the backbone riser cable. Cat5e is only sold in 25 -pair cable. Should multiple 25 -pair cables be used to meet the 50/100 pair requirement? ➢ Yes, multiple 25 -pair cables should be used to meet the pair quantity specified in the RFP. 3. Will grounding be provided or must the vendor provide grounding of all racks, ladders, etc? ➢ All telco backboards will have grounding provided as specified in the architectural plans (see section 14.20 of the RFP). However, all sites requiring rack/ladder installations will not necessarily have grounded backboards installed. Vendor is responsible for proper grounding of installation. 4. Is plenum cable required for installation? ➢ Yes, all cable installed must be plenum rated. 5. Must all fiber cable be run inner -duct? ➢ As specified in section 10.2.2 of the RFP, all fiber cable must be run inner -duct unless otherwise recommended by the manufacturer. 6. Please clarify the conference room modular outlet requirements depicted in diagram 14.2? ➢ The eight (8) conference room locations depicted in diagram 14.2 shall have a total of 6 cables each. Four (4) cables shall be home run to telco closet 2 -009, and an additional two (2) cables shall be home run to the PD computer room. 7. Which sheets should vendors receive from Miami T- square when they pick up the architectural drawings (see section 14.20 of the RFP)? ➢ The following electrical sheets: i. E.2.311 ii. E.2.312 iii. E.2.321 iv. E.2.322 v. E.2.331 vi. E.2.341 vii. E.0.100 (legend) viii. E.0.300 (additional notes) ➢ In addition, the following are the final furniture plan sheets which you may refer to if desired: i. A.2.510 ii. A.2.511 ill. A.2.520 iv. A.2.530 v. A.2.540 8. Is there a bond requirement? ➢ No, there is no bond requirement. 9. The RFP specifies Belden cable. Can another cable manufacturer be substituted in order to meet the manufacturer warranty requirements for the installation? ➢ Yes, equivalent cable may be substituted to meet the manufacturer warranty requirements. 10. What is the property address? ➢ 18070 Collins Avenue, Sunny Isles Beach. 11. Who should be contacted to obtain the architectural drawings (see section 14.20 of the RFP) ➢ Contact the Coral Gables office of Miami T- square at 305.446.8816 and speak with Helmutt, Victoria, or Lucius. If you have any problems obtaini ng the plans please contact the Architect directly — Larry Kline at 305.447.3574. 12. What is the deadline for bid submission? ➢ All sealed bids must be received by the City Clerk by 10:00 AM on May 3, 2004.