CTA Project No. 19-0035-001-01 16110-9 Golden Shores Street Lighting <br />October 12, 2020 SIB Bid No. 20-09-01 <br />K. Backfill: <br />1. Do not backfill until inspected by ENGINEER. <br />3.12 MANHOLES <br />A. Excavate, shore, brace, backfill, and final grade back to original state. <br />B. Do not install until final raceway grading has been determined. <br />C. Install such that raceways enter at nearly right angles and as near a s possible to one <br />end of wall, unless otherwise shown. <br />D. Grounding: As specified in Section 16450, GROUNDING. <br />E. Identification: Field stamp covers with manhole or handhole number as shown. Stamped <br />numbers to be 1-inch minimum height. <br />3.13 EMPTY RACEWAYS <br />A. Provide permanent, removable cap over each end. <br />B. Provide PVC plug with pull tab for underground raceways with end bells. <br />C. Provide nylon pull cord. <br />D. Identify, as specified in Paragraph IDENTIFICATION DEVICES, with waterproof tags <br />attached to pull cord at each end, and at intermediate pull point. <br />3.14 IDENTIFICATION DEVICES <br />A. Warning Tape: Install approximately 12 inches above underground or concrete - <br />encased raceways. Align parallel to, and within 12 i nches of, centerline of runs. <br />3.15 PROTECTION OF INSTALLED WORK <br />A. Protect products from effects of moisture, corrosion, and physical damage during <br />construction. <br />B. Provide and maintain manufactured watertight and dust -tight seals over all conduit <br />openings during construction. <br />C. Touch up painted conduit threads after assembly to cover nicks or scars. <br />- END OF SECTION -