Laserfiche WebLink
<br />CTA Project No. 19-0035-001-01 16120-2 Golden Shores Street Lighting <br />October 12, 2020 SIB Bid No. 20-09-01 <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A. Make parallel conductors equal in length. <br />B. Band groups of conductors together at distribution centers, pullboxes, and wireways. <br />C. Phasing: <br /> 1. Phasing for entire facility shall be Phase A, Phase B, and Phase C, with voltage <br />reaching maximum value in that order. Rotation shall be C-B-A. <br /> 2. For switchgear, motor control centers, panelboards, and other distribution and <br />motor control equipment, connect phase conductors to terminals in the order A -B-C <br />from left to right, or top to bottom, facing the circuit breakers, motor starters, or <br />panelboards. When not in conflict with the foregoing due to standard arrangement, <br />bus bars in such equipment shall be in the order A-B-C from front to back and top to <br />bottom. <br /> 3. For 3-phase, 4-wire receptacles, arrange phase connecting studs clockwise from <br />the front in the order A-B-C ground. <br /> 4. For all voltage levels of 3-phase transformers, unless otherwise required, connect <br />Phase A, B, and C to terminals marked 1, 2, and 3, respectively. <br />D. Install wire and cable in conduit. Refer to Section 16111. <br />E. Take care of pulling conductors so that insulation is not damaged. Use UL approved <br />non-petroleum base and insulating-type pulling compound as needed. <br />F. Pull wire in conduit after concrete and masonry work is complete and after moisture is <br />swabbed from conduit. <br />G. Install and test conductors in accordance with manufacturer's recommendations. <br />H. Conductors shall be continuous from outlet to outlet. <br />I. Circuit numbers shall be according to Drawings. <br />J. Where a common neutral is run for two or three "home run" circuits, connect phase <br />conductors to breakers in panels which are attached to separate phases in order that the <br />neutral conductors will carry only the unbalanced current. Neutral conductors shall be of <br />same size as phase conductors unless specifically noted otherwise. <br />K. Run conductors of same circuit in same conduit. <br />L. Run conductors of different voltage systems in separate conduits. <br />M. Do not use heavy mechanical means for pulling conductors. <br />N. Wiring in panels shall be installed in a neat fashion. <br />O. When stripping insulation from conductors, do not score or damage conductor. <br />P. All conductors of No. 10 AWG and smaller shall have solid color insulation or solid color <br />coating. <br />Q. No. 8 AWG and larger conductors shall have either solid color insulation or solid color <br />coating, or stripes, bands or hash marks of the colors indicated above. Stripes, bands or <br />hash marks may be field or factory applied.