CTA Project No. 19-0035-001-01 16450-4 Golden Shores Street Lighting <br />October 12, 2020 SIB Bid No. 20-09-01 <br />B. Interconnect ground rods by direct-buried copper cables. <br />C. Connections: <br />1. Install ground cables continuous between connections. <br />2. Exothermic welded connections to ground rods, structural steel, and buried and <br />nonaccessible connections. <br />3. Provide bolted clamp type mechanical connectors for all exposed secondary <br />connections. <br />4. Use bolded offset parapet bases or through -roof concealed base assemblies for <br />air terminal connections. <br />5. Provide electric service arrestor ground wire to water pipe when available. <br /> <br />- END OF SECTION - <br />