Laserfiche WebLink
JC RDA 149C IAUVICAL CONTRACTOR <br />CH #Ca03499 CF 5COL9060 PE 00012743 CC #0014777 <br />8011 NW W4 Street Miami, FL 331266 <br />PR (363) 262-0095. FAX (305) 597-7020 <br />PROJECT NAWIE: Sunny Isles Government Center <br />PREVENTIVE MAINTENANCE CHECKLST AND SCOPE OF WORK <br />(1) CHILLER INSPECTIONS <br />Scope of work for routine inspections on chillers: <br />A Record pertinent system temperatures, pressures, and electrical readings necessary to determine <br />the a ds" operating conditions of the system_ <br />B Check operating and safety controls of the system. <br />C Check Oil separator level and temperature <br />D Check for water and or oil leaks I make. corrections <br />E Check motor starter and or VFLI Make seise neonnections are secure <br />F check for abnormal noises or vibrations <br />G Check customer's tog with operator. discuss general operation. <br />H Report any unoorrected deficlenales. <br />Scope of work for annual inspections on chillers: <br />A Record pertinent system temperatures, pressures, and electrical readings necessary to determine <br />the ezistirlg operating conditions of the :system. t <br />B Lode out I Tag out J Isolate Condenser I Brush tubes with rotating nylon brush <br />C Open VM or Starter I Check and clean oontacts I secure connections <br />D Check and calibrate safety controls I Pressure temperature controls <br />E Meg compressor motor and oil pump motor. Record readings <br />F Tight" motor terminals, and control.panel terminals <br />G Clean oli strainers, replace filters. and gaskets wets eieluired <br />H Tighten all oil heater leads <br />I Take oil samples and have analyzed for add, moisture, and metal wear once yearly, change or7 as <br />indicated by analysis report_ <br />J Reviety 08M manual for any other maintenance proceedure <br />