Laserfiche WebLink
Miami -Dade County <br />NEED TO TEST. NEED TO LABEL ELECTRICAL PANEL FOR EM <br />LIGHTS, NFPA 101:7.8.1.2. <br />7- PROVIDE FIRE EXTIGUISHERS FOR EVERY 75 FEET OF TRAVEL <br />DISTANCE, MOUNT ON THE WALL FROM THE TOP OF EXTINGUISHER <br />TO AFF NO MORE THAN 5 FEET. NFPA 101:9.7.4.1. <br />8- HANDRAILS IN STORAGE AREA NEED TO END TO THE WALL OR <br />ITSELF OR TO THE FLOOR AT THE TOP & BOTTOM OF RAIL TO <br />PREVENT CLOTHES FROM BEING SNAGGED ON THE HANDRAIL. <br />HANDRAILS NED TO BE 34? TO 38? IN HEIGHT. NFPA 101:7.2.2.4.3. <br />9- FIRE ALARM PERMIT #2020058368- TESTING IS COMPLETED & <br />ONLY PENDING PLAN REVIEW. <br />10- PROVIDE PERMANENT SIGNAGE FOR ALL ELECTRCIAL PANEL <br />ROOMS & PUT BY THE OUTSIDE OF THAT ROOM, NEEDS TO STATE, <br />?ELECTRICIAL PANEL INSIDE, NO STORAGE?. NFPA 70:110.26 <br />11- NO STOCKING ALLOWED WITHOUT A TCO FOR STOCKING OR A <br />CO APPROVAL. <br />12- FOR ALL FIRE RATED DOORS, PROVIDE FIRE RATING LABEL ON <br />DOOR SO IT IS VISBALE. <br />NFPA 1:12.7.3.2.2. <br />13- ALL DOORS FOR EGRESS MAY NOT HAVE A KEY LOCK ON BOTH <br />SIDES. DOOR REQUIRED TO BE TURN KEY LOCKING ARRANGMENT <br />WITH NO SPECIAL KNOWLEDGE. NFPA 101:7.2.1.5.6. <br />14- ALL DOORS WITH SELF CLOSERS MUST CLOSE & LATCH. NFPA <br />101:7.2.1.8.1. <br />SRI FEES APPLY <br />LT. T. GUILER <br />Date: Inspector: Type: Status: <br />2/11/2021 Tina Guller (TINAG) 208 - FIRE TCO 7 - NOT READY FOR <br />INSPECTION INSPECTION <br />NOT READY FOR INSPECTION. CALLED CONTRACTOR AND HE DID <br />NOT NEED AN INSPECTION TODAY. HE CALLED FOR SRI THE <br />FOLLOWING DAY. <br />LT. GUILER <br />Date: Inspector: <br />Type; Status: <br />imi n. miamidade.9ov/MD FR/CommentRpt.asp?Permit=2019052832&Flan=N/ia%e, <br />4 <br />