Docusign Envelope ID: 41 F63DOF-3BC8-4149-8618-1 BBEEF49D6F7 <br />Subject Schindler Elevator Modernization Proposal - LSUN-DSPJUJ <br />Page 22 of 31 <br />Date 6/4/2024 <br />From Building Electrical Distribution Panel <br />Note 1 - Available Fault Current before disconnect <br />Label must show Available Fault Current <br />at Primary of Disconnect <br />Note 2 - Local Electricial Contractor must provide proof of building Available Faui <br />Current Calculations, Manufacturer and model of fuse <br />with supporting fuse charts to show compliance <br />of NEC Code upon request. <br />Note 3 - Available Fault Current after mitigation to be Labeled <br />-Apparent RMS Symmetrical Fault Current" at Secondary <br />of Disconnect. Must not exceed Elevator Equipment <br />rating of 5k SCCR. <br />To Elevator Equipment <br />FIGURE 1: AVAILABLE FAULT CURRENT RATING LABELLING DIAGRAM <br />