Laserfiche WebLink
Docusign Envelope ID: 41 F63DOF-3BC8-4149-8618-1 BBEEF49D6F7 <br />Subject Schindler Elevator Modernization Proposal - LSUN-DSPJUJ <br />Page 21 of 31 <br />Date 6/4/2024 <br />B. Provide one normally open dry contact (pre -transfer) to close 30 to 60 seconds <br />prior to transfer to emergency power or back to normal power. This contact <br />should reopen immediately after actual transfer of power. This is to prevent <br />transfer of power while an elevator is moving, which can occur during the return <br />to normal power or on an operating test. Provide two #12 AWG wires. <br />Note: When operating elevators on emergency power, a means of absorbing <br />the regenerative energy may be necessary and shall be provide by others. <br />It is required that the car light, the fan circuits, ascending car protection circuit <br />and the intercom circuit (if supplied), be set to operate from the emergency <br />power supply in accordance with the building code. <br />The SCCR rating of elevator equipment is 5000 Amps, contractor to ensure that the available <br />fault current of the building supply at the service switch does not exceed this value (Per NEC <br />110.10). Contractor to include a label (please see figure 2- Available Fault Current Label <br />Example) that identifies the Max Available Fault Current onto Disconnect. <br />A. See Note 1 of Figure 2, Available Fault Current Labelling Diagram. In addition, <br />we require a hard copy of the manufacturers Fuse Chart and rating verifying <br />the available fault current meets requirements. <br />B. Per NEC 110.24, the service switch should be legibly marked with Apparent <br />RMS Symmetrical fault current supplying the Elevator Equipment. **See note <br />3 of AVAILABLE FAULT CURRENT RATING LABELLING DIAGRAM. <br />NETWORK CONNECTION REQUIREMENT FOR TWO-WAY VISUAL COMMUNICATION <br />DEVICE (A17.1-2019 / B44-19 or IBC 2018) <br />A. Where the elevator rise is 18m (60 ft) or more, or seismic operation is provided <br />according to A17.1-2016 or later requirements, a single RJ45 wired Ethernet <br />communications circuit shall be provided by the building. This Ethernet <br />connection shall be located in the machine room associated with the Elevator <br />Control Visual Alarm Box for the master elevator group. <br />B. Where the elevator rise is below 18m (60ft), and seismic operation is not <br />provided according to A17.1-2016 or later requirements, separately wired RJ45 <br />Ethernet communications circuits, one per elevator group, shall be provided by <br />the building. This Ethernet connection shall be located in the machine room <br />associated with each Elevator Control Visual Alarm Box. <br />C. The network must have enough bandwidth for connecting to multiple elevators <br />and displaying a series of images with adequate resolution to identify the <br />presence and general condition of passengers in the elevator. The <br />recommended minimum upload speed is 0.5Mb/s per elevator connected to the <br />communication system. Note that networks are commonly rated by their <br />download speed with a lower upload speed. <br />D. The communications circuit shall originate at the Elevator Control Visual Alarm <br />Box, part of the two-way visual communication device designed by Schindler <br />and terminate at the building WAN internet equipment routed via a 1" conduit. <br />E. This internet connection is required to have an un -interruptible power supply <br />for a duration of 4 hours to allow for the Visual Communication Device to <br />function if building power is lost. <br />