<br />THE CITY OF SUNNY ISLES BEACH <br />PROJECT NO. 21-1011 <br />BUILDING DEPARTMENT RELOCATION TO ANNEX <br /> <br />Project No. 21-1011 November 2024 033000 Cast-in-Place Concrete-16 <br /> <br />change. <br />3. Air Content: ASTM C 231, pressure method, for normal-weight concrete; one <br />test for each composite sample, but not less than one test for each day's <br />pour of each concrete mixture. <br /> <br />4. Concrete Temperature: ASTM C 1064; one test hourly when air <br />temperature is 40 deg F and below and when 80 deg F and above, and one <br />test for each composite sample. <br /> <br />5. Compression Test Specimens: ASTM C 31. <br /> <br />a. Cast and laboratory cure one set of four standard cylinder <br />specimens for each composite sample. <br />b. Where the Contractor intends to remove load supporting forms <br />(when conditions permit), cast and field cure one set of four <br />standard cylinder specimens for each composite sample. Field <br />curing shall continue up to within four hours prior to laboratory <br />testing. The Contractor shall be responsible for the safe field <br />storage of the concrete cylinders during the field curing process. <br /> <br />6. Compressive-Strength Tests: ASTM C 39; test one laboratory-cured <br />specimen at 7 days and two specimens at 28 days. The fourth cylinder shall <br />be held for testing as a check cylinder. <br /> <br />a. A 28-day compressive-strength test shall be the average <br />compressive strength of two specimens obtained from same <br />composite sample. <br /> <br />7. Test results shall be submitted in writing to Engineer, concrete <br />manufacturer, and Contractor within 48 hours of testing. Reports of <br />compressive-strength tests shall contain: <br /> <br />a. Project identification name and number <br />b. Name of concrete testing and inspecting agency <br />c. Date of concrete placement <br />d. Date of compressive strength test <br />e. Location of concrete batch in Work Design compressive strength at <br />28 days <br />f. Mix design designation <br />g. Slump of concrete <br />h. Temperature of concrete at placement <br />i. Percent air entrained <br />j. Number of specimens tested <br />k. Compressive breaking strength <br />l. Type of break for both 7- and 28-day tests <br /> <br />8. Strength of each concrete mixture will be satisfactory if every average of any <br />three consecutive compressive-strength tests equals or exceeds specified <br />compressive strength and no compressive-strength test value falls below <br />specified compressive strength by more than 500 psi. <br /> <br />